765-1503/100-000
Commissioning
56
Product manual | Version: 2.0.0
16DO FLD EI DC 24V 2.0A
8. Then run the
RunStandAlone.bat
file.
ð
The DHCP server is now ready.
ð
In the output window, Open DHCP Server shows the query and the assigned IP ad-
dress.
10.2 Configuration
10.2.1 Configuring the Module via EtherNet/IP
For the EtherNet/IP scanner and EtherNet/IP adapter to exchange process data, you
need to configure the EtherNet/IP scanner. This requires the device description file (EDS
file) for the module used:
• wago_07651503.eds
Carry out the following steps in the configuration software of the EtherNet/IP scanner
used:
• Import the EDS file.
• Select the module from the device catalog.
• Add the module to the configuration project.
• Select a connection: connection 1, connection 2 etc.
• Set the parameters.
The individual steps are describe in detail below.
10.2.1.1 Selecting the Module
Select the module used from the device catalog.
Module: 765-1503/100-000
Designation:16 DO FLD EI 24 VDC 2.0 A
10.2.1.2 Selecting a Connection
The module offers multiple connections. Select a connection for your application. By se-
lecting the connection, you determine the following:
• Connection type: “Exclusive owner,” “Input only” or “Listen only”
• Whether or not the scanner transfers the port parameters to the product
Connection Type
The module offers multiple connection types:
• Input only: The scanner can only read input process data. This is the default connec-
tion type.
• Listen only: The scanner can only read input process data. This connection type re-
quires another scanner that establishes an “Input only” connection to the product.