765-1503/100-000
Functions
24
Product manual | Version: 2.0.0
16DO FLD EI DC 24V 2.0A
5
Functions
5.1 Process Image
This section describes the process data. The structure of the process data depends on
which connection (connection 1, connection 2 etc.) is used between the EtherNet/IP
scanner and the module. The module offers multiple connections; a connection was se-
lected during configuration of the EtherNet/IP scanner.
5.1.1 List of Connections
List of Connections
• Connection 1: Exclusive Owner
• Connection 2: Exclusive Owner without Config
• Connection 3: Listen Only
• Connection 4: Input Only
The following sections describe the process image for each connection.
5.1.2 Input Process Data of Connections 1 to 4
The following table describes the structure of the input process data of connections 1
through 4.
Table 18: Input Process Data
Byte Off-
set
Byte
Count
Input Process Data
Description
0
1
DI status
0: DI data invalid.
1–255: DI data valid.
1
1
Dummy byte
Reserved, 0
2 ... 3
2
DI data
The port and pin assignment of process data depends
on the process data layout setting: pin-based or port-
based. See the following tables.
The process data of the digital inputs can be transferred on a port basis (default) or pin
basis. The following tables show the port and pin assignment.
Table 19: Process Data of the Digital Inputs (Port-Based Assignment)
Byte Off-
set
Bit
Input Process Data
2
0
Port X01, pin 4: DI A or mirrored DO A
1
Port X01, pin 2: DI B or mirrored DO B
...
...
6
Port X04, pin 4: DI A or mirrored DO A
7
Port X04, pin 2: DI B or mirrored DO B
3
0
Port X05, pin 4: DI A or mirrored DO A
1
Port X05, pin 2: DI B or mirrored DO B
...
...
6
Port X08, pin 4: DO A
7
Port X08, pin 2: DO B