765-1205/0100-0000
Commissioning
76
Product manual | Version: 1.0.0
8DIO FLD EC DC 24V 2.0A
The following table lists port-specific configuration parameters.
Table 48: Port-Specific Configuration Parameters
Node Name
Node Class
Access Default Description
OverCurrentPin1, Over-
CurrentPin2, OverCur-
rentPin4
Variable
Read
0
Warning level for current upper limit on pin 1, pin
2 or pin 4; unit: 1 mA
0: monitoring not enabled
UnderCurrentPin1, Un-
derCurrentPin2, Under-
CurrentPin4
Variable
Read
0
Warning level for current lower limit on pin 1, pin
2 or pin 4; unit: 1 mA
0: monitoring not enabled
10.3.3.1.3 Read Process Data
The OPC UA server provides nodes with process data. For example, the OPC UA client
can read out the value on pin 2 of a port in the
Pin2ProcessData
node. The path to this
node is:
Root > Object > DeviceSet > [device name] > DigitalConnector >
PortXX > ProcessData
Note
OPC UA client can only read process output data
The process output data is written by the EtherCAT controller. The OPC UA client can
only read process output data.
The following table lists port-specific process data.
Table 49: Port-Specific Process Data
Node Name
Node Class
Access
Description
Pin2ProcessData
Variable
Read
Process data on pin 2
Pin4ProcessData
Variable
Read
Process data on pin 4
10.3.3.1.4 Read Measured Values
The OPC UA server provides nodes with calculated measured values. For example, the
OPC UA client can read out the calculated total current of supply cable 1 in the
SumCur-
rentL
node. The path to this node is:
Root > Object > DeviceSet > [device name] > DigitalConnector > Di-
agnostics > Current
The following table lists device-specific (calculated) measured values.
Table 50: Device-Specific (Calculated) Measured Values
Node Name
Node Class
Access
Description
SumCurrentL
Variable
Read
Total current in supply cable 1 calculated
from individual measurements; unit: mA
SumCurrentL2
Variable
Read
Total current in supply cable 2 calculated
from individual measurements; unit: mA
MeanTemperature
Variable
Read
Average value for the temperature of the
assembly, calculated from the temperature
values measured individually on the three
chips; unit: °C