Quick-Start
Guide
•
17
Telecontrol with CoDeSys 2.3
WAGO-I/O-SYSTEM 750
Telecontrol Quick-Start Manual
Highlight the entry "K-Bus[FIX]" in the PLC configuration, open the context
menu with the right mouse button and select "Add sub-module". This will
open the I/O configurator.
Fig. 13: WAGO-I/O-PRO CAA, I/O configuration
In the example application, as described in section 2.1, only one digital input
module 750-400, one digital output module 750-501 and one analog input
module 750-461 have been plugged into the 750-872 controller. The 750-600
end module is plugged in at the extreme right.
Consequently, now first select the module 750-400 from the "I/O Module
Catalog" under “Digital Input” on the left-hand side and transfer it to the right-
hand side in your selection using the "Insert" button.
Then select the module 750-501 from the "I/O Module Catalog" under
“Digital Output” on the left-hand side and likewise transfer it to the right-hand
side in your selection using the "Insert" button.
Then select the module 750-461 from the "I/O Module Catalog" under
“Analog Input” on the left-hand side and likewise transfer it to the right-hand
side in your selection using the "Insert" button.
If you want to delete modules from your selection, then highlight the module
concerned on the right-hand side and press "Delete".
You can change the position of a module in your selection by highlighting the
module and moving it up or down with the arrow buttons on the right-hand
side of the window.