Downloading the Program to the 750-872 Controller
WAGO-I/O-SYSTEM 750
Telecontrol Quick-Start Manual
2.6 Downloading the Program to the 750-872 Controller
Click "Online"
Æ
"Communications parameters" in the menu and create a
new communications channel. Select "TCP/IP" (3S TCP/IP driver).
Enter the IP address of your coupler (e.g., 192.168.0.3) under “Address“.
Enter 2455 as the port. The transport protocol is TCP. Confirm your entry by
clicking "OK".
Make sure
that the simulation is deactivated.
You can now transfer the program via "Online"
Æ
"Login".
Start the program via "Online"
Æ
"Start".