20 • Quick-Start Guide
Telecontrol with CoDeSys 2.3
WAGO-I/O-SYSTEM
750
Telecontrol Quick-Start Manual
This produces another sub-item "IEC 60870-5-Config[VAR]" in the system
configuration. Clicking this item opens a new window in which 2 tabs are
shown. Now open the "IEC 60870 - Config" tab.
Fig. 18: PLC configuration
The basic settings for telecontrol according to IEC 60870-5 can now be made
in this window. Set the "Create variables automatically" option to "no".
This window must also be used to define the communications protocol with
which communication is to be set up with the data server.
A choice can be made from the following communications protocols:
101 via the serial interface [Serial]
104 via the RJ-45 interface [TCP/IP]
2.4.1 Communication via the RJ-45 Interface [TCP/IP]
Highlight the required interface to the data server in the bottom left-hand box,
in this case "104 Data servers [TCP/IP]", and click the "ADD>>" button
between the bottom two boxes in order to select the communications interface.
The interface "IEC60870_Server104 [001.000 = 1]" will appear in the bottom
right-hand box under "IEC60870 configuration“.
To remove an interface which appears in the right-hand window, the interface
can be selected in this window and removed by clicking the "<<DEL" button
between the two windows.
Settings can be adjusted by highlighting the interface in the bottom right-hand
window. These are not relevant for this Quick-Start manual.