Functions
WAGO I/O System 750
750-8210/040-000 PFC200; G2; 4ETH; XTR
Manual
Version 1.7.0, valid from FW Version 04.01.10(23)
5
Functions
</dg_
5.1
Network
5.1.1
Interface Configuration
The X1, X2, X11 and X12 network interfaces of the controller are connected with
an integrated configurable 5-port switch, in which the fifth port is connected to the
CPU.
The four interfaces and configurable switch enable wiring for:
•
One common network where all four ports share a common IP address.
•
Two separate networks, each of which has two ports sharing a common IP
address.
•
Two separate networks where one port has its own IP address and three
ports share a common IP address.
•
Three separate networks: one IP address per port, plus a common IP
address for two ports.
•
Four separate networks where each port has its own IP address.
The physical interfaces (ports) are assigned via logical bridges and can be e.g.,
configured via the WBM.
Figure 16: Example of Interface Assignment via WBM
For network interfaces X1
… X<n>, fixed IP addresses can be set temporarily
(“Fix IP Address” mode). The setting is carried out with the Reset button (see
Section “Commissioning” > … > “Temporarily Setting Fixed IP Addresses”).
Setting a fixed IP address has no effect on the mode previously set.