220 Appendix
WAGO I/O System 750
750-8210/040-000 PFC200; G2; 4ETH; XTR
Manual
Version 1.7.0, valid from FW Version 04.01.10(23)
15.2.1.3.2
“BACnet Configuration” Page
You can make special settings for the BACnet fieldbus on this page.
Click the
[Submit]
button to apply a setting.
Changes made to the BACnet configuration are not applied until after a restart.
Use the WBM Reboot function to restart the stack/controller. Click the
[Restart]
button to restart the runtime. Do not shut down the controller too early!
“BACnet Service” Group
You can enable/disable the fieldbus in this group.
The “Service active” parameter must be enabled (default setting) for the BACnet
fieldbus protocol to be used.
On a runtime restart a security message is displayed in a pop-up window asking
if you really want to perform a restart.
Table 123
: WBM Page “BACnet Configuration” – “BACnet Settings” Group
Parameter
Meaning
Service active
Enable/disable the BACnet fieldbus.
Runtime restart
[Restart]
Use this button to restart the runtime.
“BACnet Settings” Group
The basic settings for the fieldbus are given in this group.
Table 124
: WBM Page “BACnet Configuration” – “BACnet Settings” Group
Parameter
Meaning
Port number
Set the port for BACnet fieldbus communication.
Who-Is online interval time
(sec)
Here, you can specify the intervals at which the
controller transmits queries to the fieldbus about
which other subscribers are online (minimum: 60
seconds).