WAGO-I/O-SYSTEM 750 XTR
Commissioning 67
750-652/040-000 Serial Interface RS-232/RS-485 XTR
Manual
Version 1.3.0
Table 49: DMX Diagnostics – Diagnostic Bits in Byte D0 of the Input Data
Bit number Name
Value
Description
7
Packet ID
0
bin
… 1
bin
0
bin
: The start code of the received
DMX packet is 0.
1
bin
: The start code of the received
DMX packet is no 0 (alternative start
code or faulty receipt).
6
Transmission
failure when
receiving
0
bin
… 1
bin
0
bin
: Receipt of a packet within 1.2 s
1
bin
: More than 1.2 s has passed since
receipt of a valid packet.
0 … 5
MaxChNum 0
dez …
21
dez
Number of DMX channels actually
received
8.3.6.3.1 “DMX Receive” Operating Parameters
Functional limitations based on different operating conditions!
The “DMX receive” function has been tested under certain operating conditions.
If the I/O module is operated in conditions other than those listed in this section, it
can lead to functional limitations and data loss.
Additional information on using DMX functions is listed in the “DMX_01
Application Note”.
The application note is available for download at the
Note the process image size setting!
In “DMX receive” mode, the correct process image size must be set.
To operate the I/O module in DMX Slave mode, the 24-byte process image size
(default) must be used!
Incorrect operating parameters can lead to functional limitations and instable
operation. Operating parameters are listed below that ensure stable operation.
•
Sender:
Compatible with DMX specification E1.11-2008/USITT DMX512-A
•
DMX transmission link:
100 m twisted-pair cable, Cat. 5, terminated with 120
Ω terminating resistors
•
Receiver:
I/O module 750-652/040-000 firmware version 06 or higher
•
Node configuration:
- Position 00: 750-881 [Version: SW 01.05.15(07) / HW 07 / FWL 03]
- Position 01: 750-652/040-000 [Version: SW 01.02.15(06) / HW 01]
Process image size: 48 Bytes
- Position 02: 750-652/040-000 [Version: SW 01.02.15(06) / HW 01]
Process image size: 24 Bytes