86 Appendix
WAGO-I/O-SYSTEM 750 XTR
750-652/040-000 Serial Interface RS-232/RS-485 XTR
Manual
Version 1.3.0
Table 60: Specific Module / Channel Parameters for 750-652/040-000
GSD File
WAGO-I/O-
CHECK
Description
Value
Selection box
Value
Parity
none
*)
Parity
none
*)
odd
Parity
odd
straight
Parity
straight
Stop bits
1
*)
Stop Bits
1
*)
2
Stop Bits
2
Flow control
deactivated
*)
Flow Control
disabled
*)
XON/XOFF
Flow Control
XON/XOFF
RTS/CTS
Flow Control
RTS/CTS
RTS, lead/follow-on time Flow Control
RTS, lead/follow-on
time
Continuous
send
lock
*)
Continuous Send Mode
disabled
*)
release
Continuous Send Mode
release
Continuous
receive
lock
*)
Continuous Receive Mode disabled
*)
release
Continuous Receive Mode release
Switching time
RS-485
100 us
*)
Switchover Time RS-485 100 us
*)
2 characters
Switchover Time RS-485 2 Characters
4 characters
Switchover Time RS-485 4 Characters
Monitoring
time con.
receive
2 characters
*)
Continuous Receive
Timeout
2 Characters
*)
4 characters
Continuous Receive
Timeout
4 Characters
*)
Default setting
con. = continuous
11.1.2.2 PROFIBUS DP Fieldbus Coupler (750-333/040-000)
The aforementioned fieldbus couplers allow module-specific configuration of
behavior at diagnosis.
Table 61: General Module / Channel Parameters
Parameter
Value
Explanation
Diagnostics channel
x
(x = 0)
0 (lock)
*)
The fieldbus coupler signals a diagnosis if the
I/O module reports the event:
• Overflow (input buffer)
Diagnostics reported by the I/O module do not
lead to the signaling of a diagnosis by the
fieldbus coupler.
1 (release)
Diagnostics reported by the I/O module lead to
the signaling of a diagnosis by the fieldbus
coupler.
*)
Default setting