34 Process Image
WAGO-I/O-SYSTEM 750 XTR
750-652/040-000 Serial Interface RS-232/RS-485 XTR
Manual
Version 1.3.0
4
Process Image
Mapping of process data in the process image of fieldbus systems
The representation of the I/O modules’ process data in the process image
depends on the fieldbus coupler/controller used. Please take this information as
well as the particular design of the respective control/status bytes from the
section “Fieldbus Specific Design of the Process Data” included in the description
concerning the process image of the fieldbus coupler/controller used.
4.1
Operating Modes for Serial Transmission
The data to be sent and received will be stored in up to 46 input and output bytes
(D0 ... D45). Data flow is controlled with control and status bytes C0 and S0 or C1
and S1. The input bytes form the memory area for up to 46 characters, which were
received by the interface. The characters to be transmitted are sent via the output
bytes.
Table 21: Process Data for Serial Transmission
Process
Image
Length
Input Data
Output Data
8 bytes S0 Status byte 0
C0 Control byte 0
S1 Status byte 1
C1 Control byte 1
D0 Data byte 0
D0 Data byte 0
D1 Data byte 1
D1 Data byte 1
D2 Data byte 2
D2 Data byte 2
…
…
D5 Data byte 5
D5 Data byte 5
24 bytes D6 Data byte 6
D6 Data byte 6
…
…
D21 Data byte 21
D21 Data byte 21
48 bytes D22 Data byte 22
D22 Data byte 22
…
…
D45 Data byte 45
D45 Data byte 45