34
Mounting
WAGO I/O SYSTEM 750 XTR
750-610/040-000 Power Supply 24 VDC Fuse Diagn XTR
Manual
Version 2.0.0
Don't forget the bus end module!
Always plug a bus end module 750-600/040-000 onto the end of the fieldbus
node! You must always use this bus end module at all fieldbus nodes with the
WAGO I/O SYSTEM 750 XTR fieldbus couplers/controllers to guarantee proper
data transfer.
For vibration loads > 4g, observe the following installation instructions:
•
Use pan-head screws or blind rivets at least every 60 mm (12 mm pin
spacing) to secure the DIN rail.
•
Make the open conductor length between strain relief and wire connection
as short as possible.
•
Use the reinforced end stop 249-197.