22 Device Description
WAGO-I/O-SYSTEM 750 XTR
750-404/040-003 Counter Adjust XTR
Manual
Version 1.1.0
Table 6: Legend for Figure “CAGE CLAMP
®
Connectors”
Designation
Connector Function
U/D
1
Frequency Counter and Up Counter:
Input for disabling and enabling the
measurement (i.e., counting is disabled when
the input is open or 0 V is present. Counting is
enabled when there is +24 V at the input.).
Up/Down Counter and Peak Time Counter:
Input for switching between upward and
downward counting (i.e., upward when switched
with 24 V, downward with 0 V).
2 Up Counter:
Second input for detecting count pulses
24 V
2
Field supply 24 VDC
0 V
3
Field supply 0 VDC
DO 1
4
Digital output DO 1
CLOCK
5
Frequency Counter:
Input for measuring the pulse period and
converting it to a frequency value
Up Counter, Up/Down Counter and Peak
Time Counter:
Input for edge-controlled detection/processing
of the count pulses, (i.e., the counter status is
incremented or decremented when the CLOCK
signal changes from 0 V to 24 V).
2 Up Counter:
First input for detecting count pulses
24 V
6
Field supply 24 VDC
0 V
7
Field supply 0 VDC
DO 2
8
Digital output DO 2