52 Commissioning
WAGO-I/O-SYSTEM 750 XTR
750-404/040-003 Counter Adjust XTR
Manual
Version 1.1.0
Data Bytes
D3
D2
D1
D0
Explanation
0x00
0x00
0x00
0x64
No count pulse received.
0x00
0x00
0x00
0x65
1
st
count pulse
0x00
0x00
0x00
0x66
2
nd
count pulse
…
…
…
…
Additional count pulses
0xFF
0xFF
0xFF
0xFF
Maximum counter status
reached.
0x00
0x00
0x00
0x00
Another count pulse results in a
count overflow.
0x00
0x00
0x00
0x01
Another count pulse received.
7.2.5
Peak Time Counter
To set the peak time counter, proceed as follows:
1.
First, make sure the counting direction is upward (input “U/D” = +24 V) and
the counter status is 0, the timer is stopped and no pulses are detected at
the input “CLOCK.”
Control Byte
Input Bit
B7
W 6
W 5
W 4 W 3 W 2 W 1
B0
Value
0
0
0
0
X
*)
X
*)
0
0
*)
Value has no relevance at this position.
Status Byte
Output Bit
B7
W 6
W 5
W 4 W 3 W 2 W 1
B0
Value
0
0
0
0
X
*)
X
*)
1
0
*)
Value has no relevance at this position.
2.
Cyclic recording is requested
. The counter status is also 0, the timer is
stopped and no pulses are detected at the input “CLOCK”:
Control Byte
Input Bit
B7
W 6
W 5
W 4 W 3 W 2 W 1
B0
Value
0
0
1
0
X
*)
X
*)
0
0
*)
Value has no relevance at this position.
Status Byte
Output Bit
B7
W 6
W 5
W 4 W 3 W 2 W 1
B0
Value
0
0
0
0
X
*)
X
*)
1
0
*)
Value has no relevance at this position.