English
Problem
Possible cause
Suggested remedy
The display shows
Not enough vacu-
um! Carry on?
Message that appears during the vac-
uum process if the pressure in the air
conditioning system after 8 min is still
more than 50 mbar.
Check the air conditioning system or
the connections between it and the A/C
service unit for leaks.
The display shows
A/C system leak-
age! Carry on?
Message at the end of the vacuum
process. The air conditioning system
shows a vacuum loss of more than
120 mbar during the checking time.
Check the air conditioning system or
the connections between it and the A/C
service unit for leaks.
The display shows
Warning! Not
enough vacuum for injection!
Message that appears during the filling
phase if the vacuum in the air condi-
tioning system is insufficient to end the
process.
Check the air conditioning system or
the connections between it and the A/C
service unit for leaks.
The display shows
Quantity too
large. Fill internal vessel!
Message that appears during the
process input if there is not enough
refrigerant in the internal container to
complete the process.
Fill the refrigerant container.
The display shows
Not enough UV.
Add!
This message appears during the fill-
ing process if there is not enough UV
additive in the container to finish the
process.
Fill the UV additive container.
The display shows
Not enough oil.
Add!
Message that appears during the filling
process if there is not enough fresh oil
in the container to finish the process.
Top up the fresh oil container with a
suitable oil type.
The display shows
Max. filling
time exceeded! Carry on?
Message that appears during the filling
process if the set amount of refrigerant
cannot be filled.
Check that A/C service unit's connec-
tions are not blocked.
The display shows
External tank
empty or closed valve. Check!
Message that appears at the start or
during the filling of the internal refriger-
ant container if the set refrigerant quan-
tity cannot be attained.
Check if the external refrigerant con-
tainer still contains enough refrigerant
or if the valves of the external refriger-
ant container are open.
The display shows
Change the
equipment drier filter! Go on?
This message appears when you
switch on the A/C service unit.
Change the internal filter as soon as
page 23). To skip this, press
ENTER
for 3 seconds.
The display shows
Change the vacu-
um pump oil! Go on?
This message appears when you
switch on the A/C service unit.
Change the vacuum pump oil as soon
on page 25). To skip this,
press
ENTER
for 3 seconds.
The display shows
Printer not in
line! Carry on?
Message indicates a printer fault.
Check if there is paper in the
printer.
Check if the printer is switched
on (yellow LED must be lit con-
stantly).
Check that the cover is closed
properly.
The display shows
Error 01
Refrigerant was added before draining
was completed.
Repeat the draining procedure; do not
interrupt it this time.
The display shows
Error 02
The air conditioning system is leaking.
There is still refrigerant in the air condi-
tioning system.
Fix the leak.
The display shows
Error 52
No USB flash drive was found/recog-
nised.
Insert the USB flash drive.
Ensure that the USB flash flash
drive has been formatted with the
FAT32 file system.
29
Содержание AirCon ASC 6100G
Страница 33: ...English 17 1 Flowchart ASC6100 G Legend 31...
Страница 36: ...English 17 2 Circuit diagram ASC6100 G 34...
Страница 37: ...English 35...
Страница 70: ...French 17 1 Organigramme ASC6100 G L gende 68...
Страница 73: ...French 17 2 Sch ma lectrique ASC6100 G 71...
Страница 74: ...French 72...
Страница 107: ...German 17 1 Flussdiagramm ASC6100 G Legende 105...
Страница 110: ...German 17 2 Schaltplan ASC6100 G 108...
Страница 111: ...German 109...
Страница 113: ...4 4 Tel 49 0 2572 879 0 5 6 Domestic 111...
Страница 114: ...Russian 6 1 112...
Страница 115: ...Russian 6 2 R1234yf 405 C R134a 743 C R153A 6 3 113...
Страница 117: ...10 Dometic 10 10 1 230 V 50 Hz 10 2 10 3 10 4 115...
Страница 118: ...11 11 1 2 3 4 5 6 7 USB 116...
Страница 119: ...Russian 8 9 10 11 12 117...
Страница 124: ...Russian 12 8 8 9 10 12 9 12 2000 g 1 STOP 2 R R1234yf L liquid 122...
Страница 137: ...Russian 10 ENTER 11 12 ENTER 13 14 15 D 16 E 17 15 Nm 18 19 20 R1234yf 133 21 133 14 4 135...
Страница 139: ...Russian 2 D E 3 I 4 G 5 J 6 J 7 H G 8 9 10 133 14 6 1 2 7783 3 137...
Страница 142: ...15 15 ENTER 8 min 50 mbar 120 mbar 134 ENTER 3 136 140...
Страница 145: ...Russian 17 1 ASC6100 G 143...
Страница 147: ...Russian V1 V2 V3 NCG V4 VC XP XP X3 UV 145...
Страница 148: ...Russian 17 2 ASC6100 G 146...
Страница 149: ...Russian 147...
Страница 183: ...Spanish 17 1 Diagrama de flujo ASC6100 G Leyenda 181...
Страница 186: ...Spanish 17 2 Esquema de conexiones ASC6100 G 184...
Страница 187: ...Spanish 185...
Страница 188: ...4445103553 2022 05 10...