LTN 6L
Operation
wc_tx000766gb.fm
49
4.19 Receptacle
See Graphic: wc_gr005140, wc_gr006328, wc_gr005141
The control panel is equipped with a convenience receptacle for
running accessories and tools from the generator. Power to this
receptacle is available any time the engine is running and the circuit
breaker is on.
NOTICE: Do not
draw more than 1660 Watts from the receptacle with
all of the lights on or the lights will turn off.
A circuit breaker
(c)
protects the Ground Fault Interrupt (GFI)
receptacle
(d)
. The GFI receptacle should be tested for proper
operation each time it is used.
To test a GFI:
Push the test button in. The reset button should pop out. Power to the
receptacle is now off. To restore power to receptacle, push reset
button in.
NOTICE:
If the reset button does not pop out, the GFI is defective.
Do
not
use the receptacle until the problem can be corrected.
If the reset button pops out during use, check the generator and
attachments for defects.