Technical Manual
WDGA with CANopen-Interface
8 - Setting-up the encoder
© Wachendorff Automation GmbH & Co. KG
45
Rev.1.24
8.3 Configuration via SDO
If not specified otherwise, all the following configurations have
to be saved into the EEPROM (8.12.1 "Saving parameters into
EEPROM").
8.3.1 SDO access on objects
You can use SDO communication to read or write on objects:
Figure 8.1: read object
The structure of a SDO message is:
Client (master) to server (encoder):
600h+ID 8
40h
04h
60h
00h
00h
00h
00h
00h
CAN-ID
DLC Command Object
L
Object
H
Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.12: Example SDO master to encoder
The payload of the SDO is 4 bytes of data (d1d2d3d4):
580h+ID 8
43h
04h
60h
00h
d4
d3
d2
d1
CAN-ID
DLC Command Object
L
Object
H
Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.13: Example SDO answer
Содержание WDGA CANopen