Technical Manual
WDGA with CANopen-Interface
8 - Setting-up the encoder
© Wachendorff Automation GmbH & Co. KG
55
Rev.1.24
The new baudrate will become effective after a reset of the
encoder (hard reset or NMT reset). Writing on object 2100h is
not protected and the change will be immediately stored in the
internal EEPROM. It is not necessary to perform a "save
parameters".
8.3.4 Node-ID selection
It is possible to change the node ID of the encoder by SDO. To set the node ID the
object 2101h, sub-Index 00h, has to be changed (only possible in Pre-Operational
state!) with a simple SDO write command:
600h+ID 8
2Fh
01h
21h
00h
Node
00h
00h
00h
CAN-ID
DLC Command Object
L
Object
H
Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.35: Node-ID selection
Valid node IDs can be:
Encoder number (d)
Node-ID (h)
1
01h
2
02h
…
…
127
7Fh
Table 8.36: Valid Node-IDs
The new node ID will become effective after an encoder reset
(hard reset or NMT reset). Writing on object 2101h is not
protected and the change will be immediately stored in the
internal EEPROM. It is not necessary to perform a "save
parameters".
Changing the Node ID automatically adjusts the PDO and
EMCY COB-IDs. After the first manual storage, they are set to
their current value and will be no longer automatically adjusted.
Performing the "Restore Defaults" command will re-enable
automatic adjustment.
Содержание WDGA CANopen