Technical Manual
WDGA with CANopen-Interface
8 - Setting-up the encoder
© Wachendorff Automation GmbH & Co. KG
43
Rev.1.24
8.2.4 End LSS configuration mode
When the configuration is completed the changed parameters must be stored and the
encoder has to be switched into PRE-OPERATIONAL state by using the following
message sequence and a final reset (e.g. a power reset):
Step 1 - store parameters:
7E5h
17h
00h
00h
00h
00h
00h
00h
00h
Table 8.6: End LSS configuration mode – Step 1 - store parameters
Step 2 - Leave configuration mode
7E5h
04h
00h
00h
00h
00h
00h
00h
00h
Table 8.7: End LSS configuration mode – Step 2 - Leave configuration mode
Step 3 - Reset (e.g. NMT "reset node" or power reset).
8.2.5 Baudrate setting
To set the baudrate send the following command:
7E5h
13h
00h
Baudrate 00h
00h
00h
00h
00h
CAN-ID
Command Sub-Index Baudrate Byte2
Byte3
Byte4
Byte5
Byte6
Table 8.8: set Baudrate
The following baud rates can be selected:
Value Baudrate
0
1 Mbit/s
1
800 kBit/s
2
500 kBit/s
3
250 kBit/s
4
125 kBit/s
5
100 kBit/s
6
50 kBit/s
7
20 kBit/s
8
10 kBit/s
9
Auto
Table 8.9: Baudrate-Coding