Technical Manual
WDGA with CANopen-Interface
8 - Setting-up the encoder
© Wachendorff Automation GmbH & Co. KG
68
Rev.1.24
8.12 Non-volatilely storage of parameters
8.12.1 Saving parameters into EEPROM
Non-volatile storage of parameters using object 1010h:
Sub-Index
Access mode
Description
0
co
Number of objects
1
wo
Save all parameters
2
wo
Save communication objects
3
wo
Save application objects
4
wo
Save manufacturer objects
Table 8.75: Saving parameters
To trigger the storage operation the "ASCII" value for "save" (in
hex: 65766173h) has to be written into the dedicated sub-
index.
E.g. "Save all Parameters":
600h+ID 8
23h
10h
10h
01h
73h
61h
76h
65h
CAN-ID
DLC Command Object
L
Object
H
Sub-
Index
Byte0
Byte1
Byte2
Byte3
Table 8.76: Example – Save all parameters