User manual - DMS9648O
69
Max
0.800
kg
Min
0.000
kg
In
0.389
mV/V
kg
1.168
Esc
%
Press “
m
” to calibrate lower limit and “
n
”
to
for the upper limit
. Press “◊%” to go back to
calibration percentage.
Value mV/V
. This calibration option is available only for strain-gauge sensors
and it is basing on the setting of correct ratio mV/V for the sensor. Process
value will be calculated considering both the entered ratio mV/V and the
effective mV/V value detected by the analogue input.
Out
2.000
mV/V
Range
6.000 kg
OK
‹
‹
Use the arrow keys to set the correct mV/V
ratio of strain gauge. Press “Ok” to confirm.
In
0.389
mV/V
kg
1.168
Esc
mV
Out
2.000
mV/V
6.000
kg
Range
Press “◊mV” to go back to setting of mV/V
ratio.
For the calibration procedure refer to the following table:
Press
Display
Do
1
Place sensor on its minimum
operating position (related to
Lower limit calibration
).