Parameter Variable
Name
Function
¾
This input network variable is used to command the Space
Comfort Controller into different occupancy modes. It is typically
set by a supervisory node to remotely control the occupancy
modes to override the local occupancy routines of the thermostat.
¾
Default Null Value: OC_NUL = 0xFF
¾
Valid
Range:
0 = OC_OCCUPIED *
1 = OC_UNOCCUPIED )
2 = OC_BYPASS –
Not Used
3 = OC_STANDY –
Not Used
Occupancy
Command
network input
SNVT_occupancy
nviOccManCmd
0xFF = OC_NUL (Release to internal occupancy)**
* OC_OCCUPIED and OC_UNOCCUPIED commands will
always have full authority over the local occupancy routines
of the thermostat may they be a local input or a PIR cover.
** OC_NUL command will release the thermostat to use its
own internal occupancy routine driven from one of the digital
input or a PIR cover installed on board.
¾
This network variable input is used to coordinate the Space
Comfort Controller with any node that may need to control the
heat/cool changeover of the unit.
¾
This input is used in conjunction with nviHeatCool and SeqOper.
¾
Default Null Value: HVAC_AUTO.
¾
This network variable is subject to the receive heartbeat time,
nciRcvHrtBt
¾
Valid
Range:
0 = HVAC_AUTO
1 = HVAC_HEAT
2 = HVAC_MRNG_WRMUP –
Not Used
3 = HVAC_COOL
4 = HVAC_NIGHT_PURGE –
Not Used
5 = HVAC_PRE_COOL –
Not Used
6 = HVAC_OFF
7 = HVAC_TEST –
Not Used
8 = HVAC_EMERG_HEAT –
Not Used
9 = HVAC_FAN_ONLY –
Not Used
12 = HVAC_MAX_HEAT –
Not Used
13 = HVAC_ECONOMY –
Not Used
14 = HVAC_DEHUMID –
Not Used
)
15 = HVAC_CALIBRATE –
Not Used
)
System Mode
network input
SNVT_hvac_mode
nviApplicMode
0xFF = HVAC_NUL –
Not Used