Note 1:
How to use nviHeatCool, nviAuxHeatEnable and SeqOpera (Sequence of Operation) variables:
Current
nviHeatCool
NviAuxHeat
Enable =
Enabled
NviAuxHeat
Enable =
Disabled
Current SeqOpera
If nviHeatCool
changed to:
New SeqOpera
2 Pipe Application
3 = HVAC_COOL
X
0 = Cooling Only
1= HVAC_HEAT
1 = Heating Only
3 = HVAC_COOL
X
2 = Cooling & Reheat
1= HVAC_HEAT
3 = Heating & Reheat
1 = HVAC_HEAT
X
1 = Heating Only
3= HVAC_COOL
1 = Cooling Only
1 = HVAC_HEAT
X
3 = Heating & Reheat
3= HVAC_COOL
2 = Cooling & Reheat
4 Pipe Application
3 = HVAC_COOL
X
0 = Cooling Only
0= HVAC_AUTO
1= HVAC_HEAT
4 = Cool/Heat 4 Pipes
1 = Heating Only
3 = HVAC_COOL
X
2 = Cooling & Reheat
0= HVAC_AUTO
1= HVAC_HEAT
5 = Cool/Heat 4P & Reheat
3 = Heating & Reheat
1 = HVAC_HEAT
X
1 = Heating Only
0= HVAC_AUTO
3= HVAC_COOL
4 = Cool/Heat 4 pipes
1 = Cooling Only
1 = HVAC_HEAT
X
3 = Heating & Reheat
0= HVAC_AUTO
3= HVAC_COOL
5 = Cool/Heat 4P & Reheat
2 = Cooling & Reheat
0 = HVAC_AUTO
X
4 = Cool/Heat 4 Pipes
1= HVAC_HEAT
3= HVAC_COOL
1 = Heating Only
0 = Cooling Only
0 = HVAC_AUTO
X
5 = Cool/Heat 4P &
Reheat
1= HVAC_HEAT
3= HVAC_COOL
3 = Heating & Reheat
2 = Cooling & Reheat