background image

mounted in the horizontal position with the arrow
pointing in the direction of gas flow. See GAS
PRESSURE REGULATOR under REMOVAL AND
REPLACEMENT OF PARTS.

See data plate for manifold pressure setting
information. Clean vent cap [1] Fig. 28 before
adjusting.

Fig. 28

1.

Connect manometer to measure gas manifold
pressure.

A.

Install a tee with hose barb connection on
the outlet side of the regulator. See
TOOLS. Connect the opposite end of tee to
the incoming gas supply for the machine.

2.

Turn gas supply on and light all pilots on the
machine.

3.

Open all valves to the full on position to light
burners and check manometer reading. The
reading should be 6" W.C. for natural gas and 10"
W.C. for propane gas. Tolerance is ±0.3" W.C.

4.

If manifold pressure is not correct, adjust the
regulator as follows.

A.

Remove the regulator closing nut [1] Fig.
29.

Fig. 29

B.

Insert a flat edge screwdriver through the
top of the regulator. While watching the
manometer, turn the adjusting screw
clockwise to increase pressure and
counterclockwise to decrease pressure until
the proper gas pressure is achieved.

C.

Install the regulator closing nut.

D.

Turn gas supply off.

E.

Remove manometer and tee from gas line.

 Clean pipe threads and apply thread

sealant that is suitable for use with propane gases.

F.

Apply thread sealant to gas line pipe threads
and re-install regulator.

INFRARED BURNER ADJUSTMENT

The only adjustment for the Infrared burner is the gas
manifold pressure. Verify the pressure is set correctly
as outlined under REGULATOR ADJUSTMENT.

INFRARED BURNER FLAME

APPEARANCE

When the Infrared burner first lights you should see a
small rolling blue flame, which will clear up after the
burner warms. Once warm, a low profile orange flame
is the best description of the Infrared burner flame. In
some cases, if the burner is operating correctly, you
may not be able to see the actual flame. Instead you
will see the glow of the ceramic bricks in the burner.

GAS ORIFICE CHECK

If burner operation seems poor and other systems
have been checked, remove MANIFOLD COVER to
access the gas and air inlet for the Ceramic-Radiant

V-SERIES HEAVY DUTY BROILERS, DOUBLE DECK AND RANGE MATCH MODELS - SERVICE PROCEDURES

AND ADJUSTMENTS

Page 13 of 16

F45548 (0715)

Содержание VBB1BF

Страница 1: ...tools instruments and skills required to perform the procedure Procedures for which you do not have the necessary tools instruments and skills should be performed by a trained Vulcan Service Technici...

Страница 2: ...BURNER 8 INFRARED BURNER 10 GAS PRESSURE REGULATOR 10 RACK SPRINGS 10 SERVICE PROCEDURES AND ADJUSTMENTS 12 PILOT FLAME HEIGHT 12 CERAMIC RADIANT BURNER AIR SHUTTER ADJUSTMENT 12 REGULATOR ADJUSTMENT...

Страница 3: ...ers Operations Manual sent with each unit The manual is also available online at www vulcanequipment com RACK POSITION AND GAS SETTING NOTE Infrared burner models must use the full gas setting knob fu...

Страница 4: ...lly Assemble the parts and retain for future use on gas equipment Pipe tee sized for the gas line inlet connection and pipe fittings pipe nipples reducers etc for the connection as required Hose barb...

Страница 5: ...must be checked for leaks Check with a soap and water solution bubbles Do not use an open flame Accessing Control Valve Upper Broiler double stack or single unit over range The side panel must be remo...

Страница 6: ...ews at the rear that are securing the back panel 1 Fig 6 and side panel to broiler frame Arrows shown in Fig 6 are pointing to the rear screw locations for right side panel removal Fig 6 D Remove side...

Страница 7: ...ilot tube fitting and remove the tube Fig 9 When disconnecting compression nut from the pilot tube fitting support the fitting to prevent damage to pilot tubing 5 Reverse procedure to install and chec...

Страница 8: ...ach burner 3 Fig 12 There are 6 ceramic bricks for each of the 3 burners 18 bricks total Fig 12 5 Remove screws securing pilot tube mounting brackets 1 Fig 13 to burner support 2 Fig 13 Position pilot...

Страница 9: ...nto the broiler grid Position 2 x 4 s underneath the burners near the front Fig 18 11 Adjust rack assembly to the middle position 12 Remove cotter pin from all three burners Fig 19 13 Grasp the bottom...

Страница 10: ...flame Clean pipe threads and apply thread sealant that is suitable for use with propane gases NOTE Gas pressure regulator should be installed as close to the broiler inlet gas connection as possible 1...

Страница 11: ...n springs Fig 24 3 Remove springs from the lifting arm mechanism and eye bolt 4 Reverse procedure to install 5 Perform RACK SPRING TENSION ADJUSTMENT V SERIES HEAVY DUTY BROILERS DOUBLE DECK AND RANGE...

Страница 12: ...stics and excessive gas consumption may occur An air shutter on the front of the burner controls the gas mixer balance A yellow streaming flame on the burner is an indication of insufficient primary a...

Страница 13: ...wise to decrease pressure until the proper gas pressure is achieved C Install the regulator closing nut D Turn gas supply off E Remove manometer and tee from gas line Clean pipe threads and apply thre...

Страница 14: ...base of the valve stem See LUBRICATION If valve grease does not improve rotation of the valve or damage is found replace the CONTROL VALVE as outlined under REMOVAL AND REPLACEMENT OF PARTS RACK SPRIN...

Страница 15: ...gas pressure 3 Control valve malfunction CERAMIC RADIANT BURNER CERAMIC RADIANT BURNER SYMPTOM POSSIBLE CAUSE Flame too yellow 1 Orifice incorrect size or dirty 2 Air shutter not adjusted correctly o...

Страница 16: ...r not lighting properly or incorrect burner flame appearance due to clogged ports 1 Broiler with Infrared burner is located too close to a fryer or charbroiler and the grease laden air is causing burn...

Отзывы: