CODE & PROBLEM
PROBABLE CAUSE
SOLUTION
Er11 - Open sensor error
Open sensor
•
Check the InP1 setup
parameter. Verify it matches
your sensor.
•
Check sensor and connections
for a reversed or open sensor. If
the condition causing the error is
resolved, the error will clear.
Er12 - Shorted sensor
•
Incorrect sensor type
•
Measuring temperature outside
the sensor range
•
Check the InP1 setup
parameter. Verify it matches
your sensor.
•
Check sensor and connections
for a reversed or open sensor. If
the condition causing the error is
resolved, the error will clear.
VC4G & VC6G SERIES FULL SIZE CONVECTION OVENS - TROUBLESHOOTING
Page 75 of 75
F24682 Rev. D (1016)