VTS2000 Series frequency inverter
- 64 -
when entering
sleep and the
set pressure
F3.15
Pipe Burst
detection
delay time
Set delay time of the pipe burst detection
0.0
~
130.0s
30.0S
○
F3.16
High pressure
detection
threshold
When the feedback pressure is greater than or equal
to this set value, the burst pipe fault "EPA0" will be
reported after F3.15 burst pipe delay. When the
feedback pressure is less than this set value, the
burst pipe fault "EPA0" will be automatically reset;
the threshold is the percentage of constant pressure.
0.0
~
200.0
%
150.0%
○
F3.17
Low pressure
detection
threshold
When the feedback pressure is less than this set
value, the burst pipe fault "EPA0" will be reported
after F3.15 burst pipe delay. When the feedback
pressure is greater than or equal to this set value, the
burst pipe fault "EPA0" will be automatically reset;
0.0
~
200.0
%
50.0%
○
Содержание VTS2000 Series
Страница 1: ...VTS2000 Series Frequency Inverter User Manual Controlling and protecting your motor...
Страница 14: ...VTS2000 Series frequency inverter 12 2 Installation and wiring 1 Dimensions...
Страница 16: ...VTS2000 Series frequency inverter 14 2 Basic wiring diagram...
Страница 21: ...VTS2000 Series frequency inverter 19 3 Operation panel introduction...
Страница 96: ......
Страница 111: ...VTS2000 Series frequency inverter 15 2 Instalacja i okablowanie 1 Wymiary...
Страница 113: ...VTS2000 Series frequency inverter 17 2 Podstawowy schemat po cze...
Страница 114: ...VTS2000 Series frequency inverter 18 3 Korespondencja skoczk w...
Страница 121: ...VTS2000 Series frequency inverter 25 3Wprowadzenie do panelu operacyjnego...
Страница 123: ...VTS2000 Series frequency inverter 27 ci stotliwo ci...
Страница 192: ......