VTS2000 Series frequency inverter
- 60 -
2: Pressure setting (MPa, Kg)
Set pressure by setting F3.01 and F3.18.
LED Hundreds: PID feedback input channel
0: AVI
1: ACI
LED thousands : PID sleep selection
0: invalid
1: Normal sleep
This method needs to set specific parameters of
F3.10
~
F3.13.
2: Disturb sleep
It is the same as the parameter setting when the sleep
mode is selected as 0. If the PID feedback value is
within the range set by F3.14, it will enter to the
disturbance sleep after maintaining the sleep delay
time. If the feedback value is less than the wake-up
threshold (PID polarity is positive), it will wake up