The inverter with a protection level of IP65 can be installed in the open air;
Detailed requirement for the installation position:
The inverter cannot be installed under direction sunshine, or the internal temperature
of the inverter will be excessively high and thus the inverter performance will be
degraded for protecting the internal elements; or even the temperature protection
will be activated by the excessively high temperature;
The inverter shall be installed in a clean environment that the environmental temper-
ature is -25 C
+ 60
O
―
;
O
C
T h e e n v i r o n m e n t a l r e l a t i v e h u m i d i t y i s n o t h i g h e r t h a n 9 5 % a n d w i t h o u t a n y
c o n d e n s a t i o n ;
For avoiding burning injury or electric shock, the inverter shall be installed beyond the
touch distance of a child. The temperature of some parts (e.g.: the heat radiator) is
quite high when the inverter is running;
Make sure the installation position will not shake;
The inverter shall be installed in a well ventilated place to ensure the normal heat
radiation;
The installation place shall be firm enough to support the inverter weight for long;
The inverter shall be installed on a vertical wall, or within 15° at most if backwards to
the wall.
Connecting terminals are located at the bottom.
Fig. 3-4: Selecting a position for installation
The inverter LCD shall be leveled with eyes and with enough space in the front for
inspection;
Installation
ShiniCube1600TL-3300TL User Manual
Victory Power New Energy
VP-UMSC1.0.0EN
11
/47