7 -
3
"AGM 2 14.7 V"
Switch Position
U1=14.70 V U2=13.60 V U3=13.20 V
1.5-5 h
24 h
Continuous
Charging program IU1oU2oU3, adapted to
closed gas-tight
AGM
(absorbed glass mat / lead-fleece batteries VRLA),
which are requiring a particularly high level U1 fur full
charging with the
indication of the charging voltage "14.7 V or 14.8 V".
It is highly recommended to check the specification
sheet of the battery concerning the high
charging voltage U1
14.7 V
!
Or else, in case of doubt, set the charging program
1 "Lead Acid/AGM
14.4 V
".
LiFePO4
Battery:
Charging program Li, charging voltage rates and temperature control adapted to lithium batteries:
The charging regulations of the battery manufacturer are absolutely to be observed!
An operation of the unit at a LiFePO4 battery without BMS Battery Management System
and without equalization charging of the cells (balancing) as well as safety circuit is not
admissible!
The battery temperature sensor must be installed at the battery (screw to the negative pole)
and connected at the unit. It serves as protection for the battery.
No function without temperature sensor, LED
"Main Charging" is flashing
!
If possible, the battery temperature should be kept above 0 °C.
4)
"LiFePO4 14.4 V"
Switch Position
U1=14.40 V U2=13.80 V U3=13.45 V
0.3-1 h
24 h
Continuous
Charging program IU1oU2oU3 adapted to
RELION types "RB" **
Super B SB12Vxx - M (Epsilon) **
MT-LiFePO4 Professional Series
of the indicated capacity rates, types with integrated
safety circuit and integrated BMS.
** also to be used with indication "Charging Voltage:
14.6 V", because of the lower battery load.
Super B SB12VxxE
GNB/Exide SL12 xxxHC with BMS
of the indicated capacity rates. Operation only with
own BMS and prescribed safety circuit!