ENGLISH
12
III.3.b.
ECR EH
:
1 or 2 speeds that can be controlled via the remote control/external control “VENTIL. MODE”
(%) »
This version (EH) is equipped with a pre heater, operated by an internal electronic controller.
Setting of a minimum speed (LS - 1/2) and a maximum speed (HS - 1/1) as %.
Equipped with factory-set timer:
(HS - 1/1) from 06:00 to 22:00
•
(LS - 1/2) from 22:00 to 6:00 for authorization to start Night Cooling.
•
Possibility to add a remote forced run control (LS - 1/2) or (HS - 1/1) (NO volt-free contacts)
Possibility to add a remote forced shutdown control (NO volt-free contacts)
III.3.c.
ECR - ECR EH
(
DIVA
®
):
Proportional ventilation control between the two speed settings (LS/HS) with CO2
management.
“AUTOMATIC CO2 CONTROL”
Setting of a minimum speed (LS - 1/2) and a maximum speed (HS - 1/1) as %. The CO2
setpoint is factory-set to 1000 ppm (in accordance with RT2012).
The transition between (LS- 1/2) and (HS - 1/1) is controlled in accordance with the CO2
level.
Equipped with continuous run factory-set timer (LS - 1/2).
Possibility to add a remote forced run control (LS - 1/2) or (HS - 1/1) (NO volt-free
contacts)
Possibility to add a remote forced shutdown control control (NO volt-free contacts)
Note: In order for the CO2 control to function correctly, the system must meet the following conditions:
Timer (HS- 1/1) on 0 (inactive) (Normal speed timer)
•
Timer (LS - 1/2) in operation (Low speed timer)
•
Forced run (HS - 1/1) and Forced shutdown not activated.
•
III.3.d.
ECR - ECR EH
(
LOBBY
®
):
Constant ventilation pressure. (Pa) “CONSTANT Pa MODE”
Setting a constant pressure (Pa).
Equipped with a timer factory-set for continuous running (LS - 1/2); Possibility to add a
remote forced run control (LS - 1/2) (NO voltage-free contacts). Possibility to add a
remote forced shutdown control (LS - 1/2) (NO voltage-free contacts).
III.3.e.
ECR - ECR EH
(
MAC2
®
):
(indisponible sur version 500 et 800)
Option of 1 or 2 CONSTANT flow rates. (m3/h) « CONSTANT MODE M3/H »
Setting of 1 or 2 constant flow rates (LS - 1/2 and HS - 1/1) (m3/h).
Equipped with a timer factory-set to:
(HS - 1/1) from 06:00 to 22:00
•
(LS - 1/2) from 22:00 to 6:00 for authorization to start Night Cooling.
•
Possibility to add a remote forced run control (LS - 1/2) or (HS - 1/1) (NO volt-free contacts)
Possibility to add a remote forced shutdown control control (NO volt-free contacts)
III.3.f.
ECR - ECR EH
(
QUATTRO
®
):
(indisponible sur version 500 et 800)
Proportional ventilation between 2 CONSTANT flow rates. (m3/h) by CO2
Setting of a minimum flow rate (LS - 1/2) and a maximum flow rate (HS - 1/1) (m3/h).
The CO2 setpoint is factory-set to 1000 ppm (in accordance with RT2012).
The transition between (LS- 1/2) and (HS - 1/1) is controlled in accordance with the
CO2 level.
Equipped with continuous run factory-set timer (LS - 1/2). (Night Cooling active)
Possibility to add a remote forced run control (LS - 1/2) (NO volt-free contacts)
Possibility to add a remote forced shutdown control (NO volt-free contacts)
Note In order for the CO2 control to function correctly, the system must meet the following conditions:
Timer (HS- 1/1) on 0 (inactive) (Normal speed timer)
•
Timer (LS - 1/2) in operation (Low speed timer)
•
Forced run (HS - 1/1) and Forced shutdown not activated.
•
Speed GV
Speed PV
Speed GV
Speed PV
Air flow PV
Air flowPV
!
!
Содержание VORT NRG 1500 ECR
Страница 40: ...ENGLISH 40 VIII APPENDICES VIII 1 Control diagram ROUE WHEEL FUSE CLAMP...
Страница 50: ...ENGLISH 50 IX NOTES...
Страница 83: ...FRAN AIS 83 VIII ANNEXES VIII 1 Sch ma de commande...
Страница 93: ...FRAN AIS 93 IX NOTES...
Страница 126: ...DEUTSCH 126 VIII ANLAGEN VIII 1 Schaltplan der Steuerung ROUE RAD MORSETTO FUSIBILE...
Страница 136: ...DEUTSCH 136 IX ACHTUNG...