III GENERAL OPERATION
III.1. GENERAL
The
VORT NRG ECR
range consists of a programme of dual-flow systems with self-regulating energy recovery, with high
efficiency and high performance, designed for service sector and industrial installations. Performance exceeds 80%.
VORT NRG ECR (
BASIC VERSION)
:
Fan management by potentiometer and wheel management by thermostats.
Cannot be used with coils.
VORT NRG ECR FIRST:
Econological management of fans and the wheel. Allows management of a non-integrated
changeover coil (or a hot water coil and/or a non-integrated cooling coil) or non-integrated electrical heater battery.
VORT NRG ECR PREMIUM BC:
Econological management of fans and the wheel. Controls an integral heating coil and
allows management of an non-integrated cooling coil.
VORT NRG ECR PREMIUM BE:
Econological management of fans and the wheel. Integral electrical heater battery and
provision for the addition of an extra non-integrated cold water coil.
III.2. OPERATING SEQUENCE
Except BASIC VERSION
Start-up sequence:
The recovery fan or VAR pressure monitoring mode starts at the same moment the fresh air damper is operated.
•
The blower fan or VAR pressure monitoring mode starts at the same moment the recovery air damper is operated.
•
Temperature control starts in accordance with the configured control mode. Electrical heating (if configured) starts on
•
the flow controller only (flow reversal). Pumps that have not yet been activated will start up.
The alarm management function is activated after the pre-set time period. At this point the system is operating
•
innormal mode.
Conditions for startup:
The system starts up when one of the following conditions is met:
The programmed schedule (timer) for normal speed or low speed operation is on “Run”.
•
The system is started manually from the CORRIGO controller.
•
One of the digital inputs for forced run is activated.
•
Shutdown sequence:
The system shutdown procedure is as follows:
Deactivation of the alarm management function.
•
Deactivation of electrical heating (if configured).
•
After a certain time interval (individually pre-set for each fan), the fans are switched off.
•
The fresh air and return air dampers are closed.
•
The signals sent to the actuators are re-set to zero and the pumps are stopped.
•
Conditions for shutdown:
The system shuts down when one of the following conditions is met:
The programmed schedule (timer) for normal speed or low speed operation is on “Stop” and the forced run signal is
•
also on “Stop”.
Activation of the external shutdown command.
•
The system is shut down manually from the CORRIGO controller.
•
Intervention of an alarm configured with the supplementary shutdown function. The system will restart automatically
•
once the alarm has been reset.
III.3. CONTROL MODES
III.3.a.
VORT NRG ECR
(BASIC VERSION)
:
1 speed that can be controlled by potentiometer
Each fan can be controlled individually by a potentiometer integrated in the system.
Possibility to add a remote forced shutdown control connected in series to the contactor (not supplied).
Содержание VORT NRG 1500 ECR
Страница 40: ...ENGLISH 40 VIII APPENDICES VIII 1 Control diagram ROUE WHEEL FUSE CLAMP...
Страница 50: ...ENGLISH 50 IX NOTES...
Страница 83: ...FRAN AIS 83 VIII ANNEXES VIII 1 Sch ma de commande...
Страница 93: ...FRAN AIS 93 IX NOTES...
Страница 126: ...DEUTSCH 126 VIII ANLAGEN VIII 1 Schaltplan der Steuerung ROUE RAD MORSETTO FUSIBILE...
Страница 136: ...DEUTSCH 136 IX ACHTUNG...