A siphon must be created in the drainage line. This must have a minimum pressure head equal to the intake pressure
of the fan, and in any case no less than 35 mm.
Water connection to the water coil
The dehumidifier must be connected to the chilled water system to ensure that thermally neutral or cooled air can be
introduced into the room.
Connect it using the 1/2” female gas connections on the unit.
N.B.
To ensure correct operation of the appliance, the unit should be supplied by a dedicated pump. You are strongly
advised to connect the unit upstream of the system's manifold so as to ensure correct water supply (fig.9).
N.B.
For correct operation of the appliance, bleed the circuit thoroughly using the bleed valves on the unit.
N.B.
The maximum permitted inlet water temperature is 50°C; the minimum permitted temperature is 10°C.
How to bleed the unit
For correct operation of the system, it is imperative to bleed
the air from the water circuit. To do this, use the bleed valve
located at the front of the unit (fig.10).