75
V.6.a. Configuration menu with admin level access
ENGLISH
Configuration
Communication
System
Port 1:
Slave
Modbus slave
communication
Port 1
Active (1)
Bacnet MSTP
communication Port
1
Active (3)
DHCP:
YES
(5)
Current Ip:
Bacnet IP
communication
Active (7)
Device name: -
(8)
BBMD address: 0
(8)
Low device ID:
2640 (8)
High device ID:
0 (8)
(x10000)
UDP low port N°
7808(8)
UDP high port N°
4(8)
(x10000)
IP -
(6)
Subnet Mask -
(6)
Subnet Mask -
(6)
Gateway -
(6)
TCP/IP
Addresses
PLA:
254 (9)
ELA:
254 (9)
Device name: -
(4)
Mac: 0
(4)
Low device ID:
2640 (4)
High device ID:
0 (4)
(x10000)
Speed:
9,600
Bps
(4)
Master max ad.:
127 (4)
Modbus address:
1 (2)
Speed:
9600
Bps
(2)
2 stop bits:
Yes (2)
Parity
No (2)
1 and 2 Activation of MODBUS RS485 and settings (see section V.8)
3 and 4 Activation of BACNET MSTP and settings (see section V.8)
5 and 6 ITCP/IP settings (see section V.8)
7 and 8 Activation of BACNET IP and settings (see section V.8)
9 Repeater addressing (see section V.8)
V.7. Modification of function parameters
V.7.a. MODBUS
A simplified MODBUS is presented at the end of the operating and commissioning instruction manual.
Access: Configuration/Communication
MODBUS TCP/IP
is activated as standard in DHCP. It is possible to know the DHCP address or set the fixed IP [(5)(6)
section V.6], Modbus port= 502/Device ID = 255
It is necessary to activate the
MODBUS RS 485
[(1) section V.6]. Possibility to set speed, parity, stop bits, etc. [(2) section
V.6].
Modbus type
1 = Coil status register (Modbus function 1, 5 and 15)
2 = Input status register (Modbus function 2)
3 = Company register (Modbus function 3, 6 and 16)
4 = Input register (Modbus function 4)