IV.19. MODBUS/WEB/BACNET connection
(refer to parameter settings in section V.6.b)
MODBUS RS485 : Use a shielded cable with twin twisted pairs, such as Belden 8723 or equivalent, to connect the BMS
to the controller (connect to port 1 (BANE)/ connect shielding to N and do not connect E)
BACS TCP/IP type BACNET :
connect to the TCP/IP port
WEB :
connect to the TCP/IP port
IV.20. Repeater connection
(refer to parameter settings in section V.6.b.2)
A repeater must be used when you connect:
• More than one control panel to the same screen (maximum 6)
• A remote control at a distance of more than 100m
In this case the remote control may be positioned at a maximum distance of 1 km. Connect the repeater and the controller
using a shielded cable with twin twisted pairs, such as Belden 8723 or equivalent. Connect a single-phase 230 V power
supply.
Connect the wires to port 1 as follows :
•
B
of the repeater to terminal B of the control panel (cable with shielded wire as shown in the diagram below)
•
A
of the repeater to terminal A of the control panel (cable with shielded wire as shown in the diagram below)
•
N
of the repeater to terminal N of the control panel (cable with shielded wire as shown in the diagram below)
Single-phase 230 V power supply to provided to the repeater.
ENGLISH
DEHUMIDIFICATION
HUMIDITY SENDER HR 010
BMS: standard
- MODBUS / RS485
- WEB / TCP/IP
- BACNET / TCP/IP
- EXO / TCP/IP
100 metres