70
V.3.b. Temperature control menu
ENGLISH
Temperature control
Ventilation control
Recovery temperature
Actual :
Sepoint :
21°C (8)
Frequency control
(ECO or DIVA)
AS manual vent.
Output:
70 (5)
%
or
VAS pressure control
(LOBBY)
Actual : 183Pa (example)
Reference :
180 Pa(5)
Frequency control
AS manual vent.
Output 1/1
70% (5)
Output 1/2
50% (5)
Frequency control
AS manual vent.
Output 1/1
180Pa (5)
Output 1/2
180Pa (5)
Frequency control
AS manual vent.
Output 1/1
70% (5)
Output 1/2
50% (5)
Frequency control
AS manual vent.
Output 1/1
180Pa (5)
Output 1/2
180Pa (5)
Frequency control
(ECO or DIVA)
AS manual vent.
Output:
70 (5)
%
or
VAS pressure control
(LOBBY)
Actual : 183Pa (example)
Reference :
180 Pa(5)
Time :
15:54 (1)
Date :
2011-01-25 (1)
Day :
Tuesday (1)
Ext. temp :
Supply temperature
Actual :
Ref.
Sepoint :
Ext. comp. setpoint
-20°C =
25°C (8)
-15°C =
24°C (8)
-10°C =
23°C (8)
Ext. comp. setpoint
-5°C =
23°C (8)
0°C =
22°C (8)
5°C =
20°C (8)
Ext. comp. setpoint
10°C =
18°C (8)
15°C =
18°C (8)
(8) Setting the setpoint temperature (see section V.4.c)
V.3.c. Ventilation control menu
(5) Speed, pressure, flow rate setting (see section V.4.b)