NC
FA2
FA1
NO
C
One 900-FA Board - Automatic Reset
Two 900-FA Boards on one power supply
Automatic Reset
NC
FA2
FA1
NO
C
NC
FA2
FA1
NO
C
NC
FA2
FA1
NO
C
One 900-FA Board - Manual Reset
Two 900-FA Boards on two power supplies
Automatic Reset
NC
FA2
FA1
NO
C
NC
FA2
FA1
NO
C
Supervision Output
Contacts Shown FA Active (open)
Fire Alarm Input
NC
C
NO
FA1
FA2
Terminal Definitions
Fire Alarm Contact
Closed = no fire
Open = fire
Manual Reset
(Temporarily close to reset)
Fire Alarm Contact
Closed = no fire
Open = fire
Fire Alarm Contact
Closed = no fire
Open = fire
Fire Alarm Contact
Closed = no fire
Open = fire
Note:
Use 18 gauge wire for all wiring. Wire
length dependent on physical layout.
Remove Jumper
Install 900-FA Here
Note:
Complete power failure shall result in a fail safe operation.
When connected to a fire alarm releasing control unit, total
loss of power for the locking mechanisms shall be configured
for a fail safe operation.
1b
IF INSTALLING TO PS902 MAIN BOARD
2
900-FA WIRING
NOTE: WHEN INSTALLATION IS COMPLETE, SECURE ENCLOSURE DOOR WITH SCREWS
OR
KEYLOCK