- WIRING EXAMPLE - FAIL SECURE
4TD
- WIRING EXAMPLE - FAIL SAFE
GND
NC2
C2
NO2
I2
NC1
C1
NO1
I1
SC
GND
NC4
C4
NO4
I4
NC3
C3
NO3
I3
SC
4RL
120/240 VAC
50/60Hz
Access
Control 2
EPT 2 or 10
EL Device 2
(not polarized)
Access
Control 1
EPT 2 or 10
EL Device 1
(not polarized)
PS914
x 4RL
Access
Control 4
EPT 2 or 10
EL Device 4
(not polarized)
Access
Control 3
EPT 2 or 10
EL Device 3
(not polarized)
Note:
To control EL1 & EL2 with Access Control 1, jumper
I1-I2
To control EL1 - EL4 with Access Control 1, jumper
I1-I2-I3-I4
0-100 ft, use 14 gauge stranded wire
0-200 ft, use 12 gauge stranded wire
Note:
Fail secure output only allowed if approved
by Authority Having Jurisdiction
GND
NC2
C2
NO2
I2
NC1
C1
NO1
I1
SC
GND
NC4
C4
NO4
I4
NC3
C3
NO3
I3
SC
4RL
120/240 VAC
50/60Hz
Access
Control 2
Mag Lock 2
Mag Lock 1
Access
Control 1
PS902
or
PS904
or
PS906
Access
Control 4
Mag Lock 4
Mag Lock 3
Access
Control 3
Note:
To control Mag Locks 1 & 2 with Access Control 1, jumper
I1-I2
To control Mag Locks 1 - 4 with Access Control 1, jumper
I1-I2-I3-I4
Refer to Wire Table
(page 7)