5
AO
- SET CONFIGURATION USING SW1 SWITCHES
SW1 SWITCH
NUMBER
AO DIP SWITCH DEFINITIONS
All switches shown in “OFF” position in wiring diagram
Set Auto Operator Signaling Option
Determines when the auto operator signal will be active
1 Off
2 Off
Operator is signaled when latch monitor switch becomes active.
Monitor switch required
1 On
2 Off
Operator is signaled 0.5 seconds after control switch
becomes active. No monitor switch used.
1 Off
2 On
Operator is signaled 1.0 seconds after control switch
becomes active. No monitor switch used.
1 On
2 On
Operator is signaled 1.5 seconds after control switch
becomes active. No monitor switch used.
Not Used
3
Not used
Set Individual Mode or Sequential Mode
Individual Mode - One input will trigger one locking device.
Sequential Mode - One input will trigger two locking devices.
4
Turn “OFF” (default) to enable Individual Mode (single doors).
Turn “ON” to enable Sequential Mode (double doors).
Set Time Delay*
(0-30 seconds, 2 second increments)
0 Sec: Switches 5-8 “OFF”
30 Sec: Switches 5-8 “ON”
5
Adds 2 seconds to the time delay when “ON”
6
Adds 4 seconds to the time delay when “ON”
7
Adds 8 seconds to the time delay when “ON”
8
Adds 16 seconds to the time delay when “ON”
DIP switches on SW1 can be turned “ON” by
moving them in the direction that the arrow is
pointing. Switches below shown in “OFF” position
* Time Delay begins when an input is released.
SW1
1 2 3 4 5 6 7 8
O N
O F F
SW1
1 2 3 4 5 6 7 8
1 2
SW2
AO INPUT / OUTPUT
TERMINAL BLOCK DEFINITIONS
Input 1
Access Control 1
Input 2
Lock Monitor 1
Input 3
Access Control 2
Input 4
Lock Monitor 2
Output 1*
Lock 1
Output 2*
AO Signal 1
Output 3*
Lock 2
Output 4*
AO Signal 2
*See page 2 for dry contacts