background image

6

SECTION 3

GENERAL REQUIREMENTS (UK)

This appliance must be installed by a competent person
in accordance with the Gas Safety (Installation & Use)
Regulations.

3.1 RELATED DOCUMENTS

The installation of this boiler must be in accordance with
the relevant requirements of the Gas Safety (Installation &
Use) Regulations, the local building regulations, the current
I.E.E. wiring regulations, the bylaws of the local water
undertaking, the Building Standards (Scotland) Regulation,
and Building Standards (Northern Ireland) Regulations.
It should be in accordance also with any relevant
requirements of the local authority and the relevant
recommendations of the following British Standard Codes
of Practice.

3.2 LOCATION OF APPLIANCE

The appliance may be installed in any room or internal
space, although particular attention is drawn to the
requirements of the current I.E.E. wiring regulations, and
in Scotland, the electrical provisions of the Building
Regulations, with respect to the installation of the appliance
in a room or internal space containing a bath or shower.

When an appliance is installed in a room or  internal space
containing a bath or shower, the appliance or any control
pertaining to it must not be within reach of a person using
the bath or shower.

The location chosen for the appliance must permit the
provision of a safe and satisfactory flue and termination.
The location must also permit an adequate air supply for
combustion purposes and an adequate space for servicing
and air circulation around the appliance. Where the
installation of the appliance will be in an unusual location
special procedures may be necessary, BS 6798 gives
detailed guidance on this aspect.

A compartment used to enclose the appliance must be
designed and constructed specifically for this purpose. An
existing compartment/cupboard may be utilised provided
that it is modified to suit.

Details of essential features of compartment/cupboard
design including airing cupboard installations are given in
BS 6798. This appliance is not suitable for external
installation.

3.3 GAS SUPPLY

The gas meter – as supplied by the gas supplier – must be
checked to ensure that it is of adequate size to deal with
the maximum rated input of all the appliances that it
serves. Installation pipes must be fitted in accordance with
BS 6891.
Pipe work from the meter to the appliance must be of
adequate size. Pipes of a smaller size than the appliance
gas inlet connection must not be used. The installation
must be tested for soundness in accordance with BS6891.
If the gas supply serves more than one appliance, it must
be ensured that an adequate supply is maintained to each
appliance when they are in use at the same time.

3.4 FLUE SYSTEM

The terminal should be located where the dispersal of
combustion products is not impeded and with due regard
for the damage and discoloration that may occur to building
products located nearby. The terminal must not be located
in a place where it is likely to cause a nuisance (see fig. 4).
In cold and/or humid weather, water vapour will condense
on leaving the terminal; the effect of such pluming must be
considered.

If installed less than 2m above a pavement or platform to
which people have access (including balconies or flat
roofs) the terminal must be protected by a guard of durable
material. The guard must be fitted centrally over the
terminal. Refer to BS 5440 Part 1, when the terminal is 0.5
metres (or less) below plastic guttering or 1 metre (or less)
below painted eaves.

3.5 AIR SUPPLY

The following notes are intended for general guidance only.
This appliance is a room-sealed, fan-flued boiler,
consequently it does not require a
Permanent air vent for combustion air supply.
When installed in a cupboard or compartment, ventilation
for cooling purposes is also not required.

3.6 WATER CIRCULATION

Detailed recommendations are given in BS 5449 Part 1 and
BS 6798. The following notes are for general guidance
only.

3.6.1 PIPEWORK

It is recommended that copper tubing to BS 2871 Part 1 is
used in conjunction with soldered capillary joints.
Where possible pipes should have a gradient to ensure air
is carried naturally to air release points and that water flows
naturally to drain cocks.

Except where providing useful heat, pipes should be
insulated to avoid heat loss and in particular to avoid the
possibility of freezing. Particular attention should be paid
to pipes passing through ventilated areas such as under
floors, loft space, and void areas.

3.6.2 AUTOMATIC BY-PASS

Vokera recommend that an automatic bypass is installed
to ensure the required minimum flow-rate is achieved at all
times. Additionally, the design of the system and its
controls should ensure that an adequate temperature
differential is met, and should be such that it prevents
boiler ‘cycling’.

BS 5440

BS 5440

BS 5449

BS 6798

BS 6891

PART 1

PART 2

PART 1

FLUES

FLUES & VENTILATION

FORCED CIRCULATION HOT WATER SYSTEMS

INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW

LOW PRESSURE INSTALLATION PIPES

Содержание Mynute VHE

Страница 1: ...INSTRUCTIONS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK My...

Страница 2: ...he system 17 5 4 Initial flushing of the system 17 5 5 Pre operation checks 17 5 6 Initiallighting 17 5 7 Checking gas pressure combustion analysis 17 5 8 Final flushing of the heating system 17 5 9 S...

Страница 3: ...chnical helpline for advice should you wish to use the Mynute VHE on a sealed pressurised system This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet...

Страница 4: ...e temperature selector clockwise to increase the boiler outlet temperature or counter clockwise to reduce the outlet flow temperature 2 digit LED display Displays the current outlet temperature of the...

Страница 5: ...cuitry to ensure flame stability at the burner Once successful ignition has been achieved the electronic circuit increases the gas rate to 75 for a period of 15 minutes Thereafter the boiler s output...

Страница 6: ...sumption Watts 75 Supply V Hz 230 50 Internal fuse 3 15A T for PCB 3 15A F for connections block External fuse 3A 2 7 Flue Details concentric 60 100 Maximum horizontal flue length 60 100mm 7 8m Maximu...

Страница 7: ...ternal external corner or boundary 300 mm I Above ground roof or balcony level 300 mm J From a surface or boundary facing the terminal 1200 mm K From a terminal facing a terminal 1200 mm L From an ope...

Страница 8: ...pes of a smaller size than the appliance gas inlet connection must not be used The installation must be tested for soundness in accordance with BS6891 If the gas supply serves more than one appliance...

Страница 9: ...um heat exchangers is used to protect the boiler and system from the effects of corrosion and or electrolytic action The inhibitor must be administered in strict accordance with the manufacturers inst...

Страница 10: ...tres The distance between the bottom of the F E tank and the highest point of the safety vent pipe must be no less than 500mm The supply of water to the F E tank should be taken from themainswatersupp...

Страница 11: ...people have access including balconies or flat roofs theterminalmustbeprotectedbyaguardofdurable material The guard must be fitted centrally over the terminal RefertoI S 813 whentheterminalis0 5metres...

Страница 12: ...e shall be unrestricted 3A 11 2 ALTERNATIVE CLOSE COUPLED ARRANGEMENT If necessary or if preferred a close coupled arrangement for the feed and expansion pipe work can be used as an alternative to a c...

Страница 13: ...Careshouldbe exercisedwhendeterminingthepositionoftheappliance with respect to hidden obstructions such as pipes cables etc When the position of the appliance has been decided using the template supp...

Страница 14: ...Connect the required number of flue extensions or bends up to the maximum equivalent flue length to the flue terminal see fig 7 8 The flue system should have a minimum of 1 maximum of3 risefromtheboil...

Страница 15: ...17mm per 1000mm NOTE When cutting an extension to the required length you must ensure that the excess is cut from the plain end of the extension see fig 8 Remove any burrs and check that any seals ar...

Страница 16: ...verter box ensuring that the exhaust pipe connects to theexhaustconnectionontheconcentrictotwinconverter Ifnecessarycuttheplainends male ofthetwinfluepipes to allow connection to the concentric to twi...

Страница 17: ...ions 4 6 3 CONDENSE PIPE During normal operation the boiler produces condense which is collected in a trap located in the lower part of the boiler A flexible pipe condense outlet pipe is connected to...

Страница 18: ...wiringdiagrams in section 8 for more detailed information 4 7 3 CONNECTINGTHE MAINS 230V INPUT fig 16 Locateandremovethescrewssecuringtheterminalblock cover 230V Pass the supply cable through the cabl...

Страница 19: ...properly filled and vented Ensure the flue system has been fitted properly and in accordance with the instructions 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on En...

Страница 20: ...user Failure to install and commission the appliance to the manufacturers instructions may invalidate the warranty 5 12 INSTRUCTINGTHE USER Hand over all documentation supplied with this appliance inc...

Страница 21: ...ssary the condense trap to ensurecorrectoperation 6 3 REPLACEMENTOFCOMPONENTS Althoughitisanticipatedthatthisappliancewillgiveyears ofreliable troublefreeservice thelifespanofcomponents willbedetermin...

Страница 22: ...NESS CHECK MUST BE CARRIEDOUT 6 11 ELECTRODES CONDENSE SENSOR fig 22 Carry out component removal procedure as described in 6 4 Unclip and remove the air chamber front and RH side covers Disconnect the...

Страница 23: ...bly A locateand remove the 3 external nuts B Replace in the reverse order Ensure all seals are in good condition taking care to ensure they are replaced correctly C Fig 27 A B B A Fig 28 6 15 CONDENSE...

Страница 24: ...wherebyonlythepump will run for 15 seconds then off for 15 seconds and will not fire until this period has elapsed 7 2 3 HEATING MODE WiththeselectorswitchintheONpositionandanyadditional controls time...

Страница 25: ...dswitchtheboilertotheOFFmode To adjust the gas valve you must first ensure that the fan Fig 30 Maximum screw Minimum screw Compensation pipe connection 7 4 2 GAS VALVE MINIMUM SETTING Locate and gentl...

Страница 26: ...mp 0 C 75 CO function time 15 min Flow NTC max temp 0 C 87 High limit thermostat 0 C 97 Burner thermostat 0 C 170 Maximum differential 0 C 35 IGNITION CONTROL VALUE Ignition attempts before L O lockou...

Страница 27: ...verted Final Reset check pump ensure there is sufficient return sensor temperature higher than circulation around heating circuit s thermistors flowsensor temperature AL34 Fan tacho signal fault Final...

Страница 28: ...e channel voltage free time clocks Programmableroomthermostats Externaltwin channelprogrammers Theappliancecan be used in conjunction with typical S Plan Y Plan systems see 8 4 1 8 4 2 please contact...

Страница 29: ...ormer FS Flow thermistor NTC RS Return thermistor NTC AD02A Main PCB CN1 CN5 Connection to PCB high voltage X4 X9 Connection to PCB low voltage F O H T Flow over heat thermostat H E T Heat exchanger t...

Страница 30: ...28 FUNCTIONALDIAGRAM 8 4 1 S Plan with Vokera 2 channel programmer 8 4 2 Y Plan with Vokera 2 channel programmer Fig 33 Fig 34 N L E...

Страница 31: ...E 1 Frame assembly 01005496 18 Cover assembly 10028554 20 Printed circuit board 10029717 21 Led light guide 10028557 26 Instrumental panel 10028551 27 Knob assembly 10028559 31 Case Assembly 01005497...

Страница 32: ...30 Table 2 200 27 200 27 200 580 200 580 36 25 200 200 POS DESCRIPTION 20VHE 25 Pipe 10029590 27 Pipe 10029592 36 Pipe 10029591 200 Washer 5023 580 Connection M 3 4 3 4 10029526...

Страница 33: ...267 9 Pipe 10029515 17 Air venting plug 10029306 25 Siphon 10028405 26 Flexible pipe 10028540 27 Flexible pipe 10027192 71 Pipe 10028430 72 Drain tap 01005137 73 Cock 10028431 247 Washer 5203 476 O ri...

Страница 34: ...de 10027864 6 Condense electrode 10026316 12 Gas pipe 10029607 13 Gas valve 10028538 15 3 4 gas cock 10020897 16 Cover for air box 10028345 19 Glass stopper assembly 10026328 27 Plug 10023805 35 Air g...

Страница 35: ...exchanger assembly 01005443 7 Conveyor 10028536 12 Flue drain connection 10028421 475 Washer 125 10026323 482 Washer 10026366 487 Washer 60 10026345 509 High limit thermostat 10026982 552 Washer 60 10...

Страница 36: ...Maximumgasrate 1 55 kg hr Minimumgasrate 0 39 kg hr Injectorsize 3 6 mm Efficiency SEDBUK 92 6 Band A Emissions CO max mg kWh 215 0 mg kWh CO min mg kWh 10 8 mg kWh NOx max mg kWh 97 1 mg kWh NOx min...

Страница 37: ...appliance data badge 10 7 1 CHECKING ADJUSTINGTHEAPPLIANCEFAN SPEEDS Move the selector switch to the OFF position and remove the 3 selector knobs 10 7 2 ABSOLUTE MAX FAN SPEED LocatetheMAXtrimmer fig...

Страница 38: ...HAT TYPE OF SCALE REDUCER HAS BEEN FITTED FOR THE DOMESTIC HOT WATER MODE MEASURE RECORD GAS RATE 3 hr MAXIMUM BURNER OPERATING PRESSURE IF APPLICABLE mbar COLD WATER INLET TEMPERATURE C HOT WATER OUT...

Страница 39: ...CARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No...

Страница 40: ...es vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 099 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the...

Отзывы: