background image

23

Fig. 29

7.3.6 FAN SPEED TABLE

Use the following table to set the corresponding fan speeds
that are relative to the appliance you are working on.

FAN SPEED (rpm) TABLE

MODEL

MAX

MIN

HTG

IGN

20HE

5.400

1.700

5.400

3.700

7.3 APPLIANCE FAN SPEEDS

The appliance fan speeds require to be checked and/or
adjusted prior to making any adjustments to the gas valve
or if the main PCB has been replaced.

ATTENTION

Gas type and appliance fan speed (output) 

must be set

according to the specific appliance specification. Vokera
accepts no responsibility if the gas type and/or fan speed
is not correctly adjusted according to the respective
appliance specification as detailed on the appliance data
badge.

7.3.1 CHECKING/ADJUSTING THE APPLIANCE FAN

SPEEDS

Move the selector switch to the OFF position and remove
the 3-selector knobs.

7.3.2 ABSOLUTE MAX FAN SPEED

Locate the MAX trimmer (fig. 29) and gently adjust
clockwise or counter clockwise to achieve the correct fan
speed (see table 7.3.6).  NOTE, the display shows the fan
RPM in multiples of 100, i.e. 25 = 2500RPM.

7.3.3 ABSOLUTE MIN FAN SPEED

Locate the MIN trimmer (fig. 36) and gently adjust
clockwise or counter clockwise to achieve the correct fan
speed (see table 7.3.6). NOTE, the display shows the fan
RPM in multiples of 100, i.e. 25 = 2500RPM.

7.3.4 IGNITION FAN SPEED

Locate the IGN trimmer (fig. 29) and gently adjust
clockwise or counter clockwise to achieve the correct fan
speed (see table 7.3.6). NOTE, the display shows the fan
RPM in multiples of 100, i.e. 25 = 2500RPM.

7.3.5 HEATING FAN SPEED

Locate the HTG trimmer (fig. 29) and gently adjust
clockwise or counter clockwise to achieve the correct fan
speed (see table 7.3.6). NOTE, the display shows the fan
RPM in multiples of 100, i.e. 25 = 2500RPM.

7.4 CHECKING THE  CO

2

 AND ADJUSTING THE GAS

VALVE

THE GAS VALVE MUST BE SET-UP OR ADJUSTED
WITH THE AID OF A PROPERLY CALIBRATED FLUE
GAS ANALYSER.
Isolate the appliance from the electrical supply and remove
the appliance casing as described in 4.7.1. Set the flue gas
analyser to read CO

2

 and insert the probe into the flue

analysis test point (

A, B 

fig. 28). Restore the electrical

supply to the boiler and switch the boiler to the OFF mode.
To adjust the gas valve you must first ensure that the fan

Fig. 30

Maximum

screw

Minimum

screw

Compensation

pipe connection

7.4.2 GAS VALVE MINIMUM SETTING

Locate and gently turn the HTG trimmer till the minimum
value (fan speed) is obtained and check that it corresponds
with the appropriate CO

2

 value (Minimum) for the respective

appliance. If the CO

2

 reading is correct, rotate the HTG

trimmer until the correct value is obtained for the respective
appliance (see fan speed table) and proceed to 7.4.3.
However, if the CO

2

 reading is incorrect, the minimum gas

pressure must be adjusted as follows:

Using a 2,5mm Allen key, very slowly turn the minimum
adjustment screw (see fig. 30) – clockwise to increase,
counter clockwise to decrease - until the correct value is
displayed on the CO

2

 analyser (allow time for the

analyser to stabilise).

7.4.3 COMPLETION

On completion of the combustion analysis check and/or
any gas valve adjustment, set the HTG trimmer to the
corresponding value as detailed in the fan speed table.
Refit the 3-selector knobs and move the mode selector to
the OFF position. Remove the test probe from the test
point and refit the sealing screw/s and/or cap.

IMPORTANT

A GAS SOUNDNESS CHECK MUST BE CARRIED OUT
IF ANY GAS CARRYING COMPONENTS HAVE BEEN
REMOVED, REPLACED, OR DISTURBED.

speed potentiometers (trimmers) have been set correctly
(see 7.3).
When carrying out a combustion analysis test and/or
adjusting the gas valve, you must ensure that all radiators
and heating circuits are fully open in order to dissipate
heat.
Remove the 3-selector knobs, locate and press the CO
button (see fig. 29). The appliance will now operate in CO
mode for approximately 15-minutes (see 7.10).

7.4.1 GAS VALVE MAXIMUM SETTING

Locate and gently turn the HTG trimmer till the maximum
value (fan speed) is obtained and check that it corresponds
with the appropriate CO

2

 value (Maximum) for the

respective appliance. If the CO

2

 reading is correct, proceed

to gas valve minimum setting (7.4.2).
However, if the CO

2

 reading is incorrect, the maximum gas

pressure must be adjusted as follows:

Using a suitable screwdriver, very slowly turn the
maximum adjustment screw (see fig. 30) – clockwise to
decrease, counter clockwise to increase – until the
correct value is displayed on the CO

2

 analyser (allow

time for the analyser to stabilise).

UNUSED

Содержание Mynute VHE

Страница 1: ...INSTRUCTIONS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK My...

Страница 2: ...he system 17 5 4 Initial flushing of the system 17 5 5 Pre operation checks 17 5 6 Initiallighting 17 5 7 Checking gas pressure combustion analysis 17 5 8 Final flushing of the heating system 17 5 9 S...

Страница 3: ...chnical helpline for advice should you wish to use the Mynute VHE on a sealed pressurised system This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet...

Страница 4: ...e temperature selector clockwise to increase the boiler outlet temperature or counter clockwise to reduce the outlet flow temperature 2 digit LED display Displays the current outlet temperature of the...

Страница 5: ...cuitry to ensure flame stability at the burner Once successful ignition has been achieved the electronic circuit increases the gas rate to 75 for a period of 15 minutes Thereafter the boiler s output...

Страница 6: ...sumption Watts 75 Supply V Hz 230 50 Internal fuse 3 15A T for PCB 3 15A F for connections block External fuse 3A 2 7 Flue Details concentric 60 100 Maximum horizontal flue length 60 100mm 7 8m Maximu...

Страница 7: ...ternal external corner or boundary 300 mm I Above ground roof or balcony level 300 mm J From a surface or boundary facing the terminal 1200 mm K From a terminal facing a terminal 1200 mm L From an ope...

Страница 8: ...pes of a smaller size than the appliance gas inlet connection must not be used The installation must be tested for soundness in accordance with BS6891 If the gas supply serves more than one appliance...

Страница 9: ...um heat exchangers is used to protect the boiler and system from the effects of corrosion and or electrolytic action The inhibitor must be administered in strict accordance with the manufacturers inst...

Страница 10: ...tres The distance between the bottom of the F E tank and the highest point of the safety vent pipe must be no less than 500mm The supply of water to the F E tank should be taken from themainswatersupp...

Страница 11: ...people have access including balconies or flat roofs theterminalmustbeprotectedbyaguardofdurable material The guard must be fitted centrally over the terminal RefertoI S 813 whentheterminalis0 5metres...

Страница 12: ...e shall be unrestricted 3A 11 2 ALTERNATIVE CLOSE COUPLED ARRANGEMENT If necessary or if preferred a close coupled arrangement for the feed and expansion pipe work can be used as an alternative to a c...

Страница 13: ...Careshouldbe exercisedwhendeterminingthepositionoftheappliance with respect to hidden obstructions such as pipes cables etc When the position of the appliance has been decided using the template supp...

Страница 14: ...Connect the required number of flue extensions or bends up to the maximum equivalent flue length to the flue terminal see fig 7 8 The flue system should have a minimum of 1 maximum of3 risefromtheboil...

Страница 15: ...17mm per 1000mm NOTE When cutting an extension to the required length you must ensure that the excess is cut from the plain end of the extension see fig 8 Remove any burrs and check that any seals ar...

Страница 16: ...verter box ensuring that the exhaust pipe connects to theexhaustconnectionontheconcentrictotwinconverter Ifnecessarycuttheplainends male ofthetwinfluepipes to allow connection to the concentric to twi...

Страница 17: ...ions 4 6 3 CONDENSE PIPE During normal operation the boiler produces condense which is collected in a trap located in the lower part of the boiler A flexible pipe condense outlet pipe is connected to...

Страница 18: ...wiringdiagrams in section 8 for more detailed information 4 7 3 CONNECTINGTHE MAINS 230V INPUT fig 16 Locateandremovethescrewssecuringtheterminalblock cover 230V Pass the supply cable through the cabl...

Страница 19: ...properly filled and vented Ensure the flue system has been fitted properly and in accordance with the instructions 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on En...

Страница 20: ...user Failure to install and commission the appliance to the manufacturers instructions may invalidate the warranty 5 12 INSTRUCTINGTHE USER Hand over all documentation supplied with this appliance inc...

Страница 21: ...ssary the condense trap to ensurecorrectoperation 6 3 REPLACEMENTOFCOMPONENTS Althoughitisanticipatedthatthisappliancewillgiveyears ofreliable troublefreeservice thelifespanofcomponents willbedetermin...

Страница 22: ...NESS CHECK MUST BE CARRIEDOUT 6 11 ELECTRODES CONDENSE SENSOR fig 22 Carry out component removal procedure as described in 6 4 Unclip and remove the air chamber front and RH side covers Disconnect the...

Страница 23: ...bly A locateand remove the 3 external nuts B Replace in the reverse order Ensure all seals are in good condition taking care to ensure they are replaced correctly C Fig 27 A B B A Fig 28 6 15 CONDENSE...

Страница 24: ...wherebyonlythepump will run for 15 seconds then off for 15 seconds and will not fire until this period has elapsed 7 2 3 HEATING MODE WiththeselectorswitchintheONpositionandanyadditional controls time...

Страница 25: ...dswitchtheboilertotheOFFmode To adjust the gas valve you must first ensure that the fan Fig 30 Maximum screw Minimum screw Compensation pipe connection 7 4 2 GAS VALVE MINIMUM SETTING Locate and gentl...

Страница 26: ...mp 0 C 75 CO function time 15 min Flow NTC max temp 0 C 87 High limit thermostat 0 C 97 Burner thermostat 0 C 170 Maximum differential 0 C 35 IGNITION CONTROL VALUE Ignition attempts before L O lockou...

Страница 27: ...verted Final Reset check pump ensure there is sufficient return sensor temperature higher than circulation around heating circuit s thermistors flowsensor temperature AL34 Fan tacho signal fault Final...

Страница 28: ...e channel voltage free time clocks Programmableroomthermostats Externaltwin channelprogrammers Theappliancecan be used in conjunction with typical S Plan Y Plan systems see 8 4 1 8 4 2 please contact...

Страница 29: ...ormer FS Flow thermistor NTC RS Return thermistor NTC AD02A Main PCB CN1 CN5 Connection to PCB high voltage X4 X9 Connection to PCB low voltage F O H T Flow over heat thermostat H E T Heat exchanger t...

Страница 30: ...28 FUNCTIONALDIAGRAM 8 4 1 S Plan with Vokera 2 channel programmer 8 4 2 Y Plan with Vokera 2 channel programmer Fig 33 Fig 34 N L E...

Страница 31: ...E 1 Frame assembly 01005496 18 Cover assembly 10028554 20 Printed circuit board 10029717 21 Led light guide 10028557 26 Instrumental panel 10028551 27 Knob assembly 10028559 31 Case Assembly 01005497...

Страница 32: ...30 Table 2 200 27 200 27 200 580 200 580 36 25 200 200 POS DESCRIPTION 20VHE 25 Pipe 10029590 27 Pipe 10029592 36 Pipe 10029591 200 Washer 5023 580 Connection M 3 4 3 4 10029526...

Страница 33: ...267 9 Pipe 10029515 17 Air venting plug 10029306 25 Siphon 10028405 26 Flexible pipe 10028540 27 Flexible pipe 10027192 71 Pipe 10028430 72 Drain tap 01005137 73 Cock 10028431 247 Washer 5203 476 O ri...

Страница 34: ...de 10027864 6 Condense electrode 10026316 12 Gas pipe 10029607 13 Gas valve 10028538 15 3 4 gas cock 10020897 16 Cover for air box 10028345 19 Glass stopper assembly 10026328 27 Plug 10023805 35 Air g...

Страница 35: ...exchanger assembly 01005443 7 Conveyor 10028536 12 Flue drain connection 10028421 475 Washer 125 10026323 482 Washer 10026366 487 Washer 60 10026345 509 High limit thermostat 10026982 552 Washer 60 10...

Страница 36: ...Maximumgasrate 1 55 kg hr Minimumgasrate 0 39 kg hr Injectorsize 3 6 mm Efficiency SEDBUK 92 6 Band A Emissions CO max mg kWh 215 0 mg kWh CO min mg kWh 10 8 mg kWh NOx max mg kWh 97 1 mg kWh NOx min...

Страница 37: ...appliance data badge 10 7 1 CHECKING ADJUSTINGTHEAPPLIANCEFAN SPEEDS Move the selector switch to the OFF position and remove the 3 selector knobs 10 7 2 ABSOLUTE MAX FAN SPEED LocatetheMAXtrimmer fig...

Страница 38: ...HAT TYPE OF SCALE REDUCER HAS BEEN FITTED FOR THE DOMESTIC HOT WATER MODE MEASURE RECORD GAS RATE 3 hr MAXIMUM BURNER OPERATING PRESSURE IF APPLICABLE mbar COLD WATER INLET TEMPERATURE C HOT WATER OUT...

Страница 39: ...CARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No...

Страница 40: ...es vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 099 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the...

Отзывы: