background image

22

7.1 CHECKING APPLIANCE OPERATION

When carrying out any repairs or servicing to the appliance, the
relevant commissioning procedure must be undertaken to
ensure the continued safe operation of the appliance. Particular
attention should be made to ensure gas soundness, water
soundness, and the electrical integrity of the appliance.

7.2 APPLIANCE MODES OF OPERATION
NOTE

The 2-digit display can show several different modes of
operation:

OFF mode

Frost protection mode active

Combustion analysis mode active

Autostop function active

Normal heating request (example 60

o

C).

Purge cycle mode.

SECTION 7        CHECKS, ADJUSTMENTS AND FAULT FINDING

7.2.1 SELECTOR SWITCH IN THE OFF/STANDBY

POSITION

When the selector switch is in the OFF/STANDBY position,
the following functions are active.

Active functions

:

Frost-protection system

Pump anti-block

7.2.2 ON-BOARD FUNCTIONS

AUTOSTOP:

 Further information on the AUTOSTOP

function, can be obtained from your local Vokera Sales
Representative.

CO FUNCTION:

 The CO function when activated, will

allow the appliance to run at maximum and minimum
output whilst a combustion analysis check is being
carried out. Whilst the CO function is active, all other
functions are disabled (minimum power operating period,
anti-cycle, set-point, etc). Once enabled, the CO function
will remain active for a 15-minute period, or until the
function is manually deactivated

FROST-PROTECTION: 

this function is only active when

there are no requests for heating or HW. If the temperature
drops below 5°C, the boiler will operate on minimum
power until the temperature of the primary thermistor

reaches 35°C. Thereafter the pump & fan will over-run for
five minutes.

ANTI-CYCLE FUNCTION:

 The anti-cycle function ensures

the burner remains switched off for at least 5-minutes after
the set-point hysterisis (set-point + 2 -8 °C).

PUMP ANTI-BLOCK FUNCTION: 

when there has been

no heating or HW request for 24-hours, the anti-block
cycle is activated. The pump will be activated for a
period of 30-seconds.

PUMP DISCHARGE FUNCTION: 

at the end of any

power on, the boiler makes an ON/OFF pump cycle
(about 2 minutes). Only at the end of this procedure the
boiler can satisfy any kind of CH requests.

PUMP CYCLE MODE: 

wen power is restored to the PCB

and/or the PCB is powered for the first time, the appliance
will enter a 2-minute purge cycle whereby only the pump
will run for 15-seconds then off for 15-seconds and will
not “fire” until this period has elapsed.

7.2.3 HEATING MODE

With the selector switch in the ON position and any additional
controls (time clock, programmer, room thermostat, etc,)
calling for heat, the appliance will operate in the heating
mode. The external pump and fan will be activated via the
flow temperature sensor. When the fan is sensed to be
operating correctly (tacho signal), the ignition sequence
commences. Ignition is sensed by the electronic circuitry to
ensure flame stability at the burner. Once successful ignition
has been achieved, the electronic circuitry increases the
gas rate to 75% of the MAX Heating (set by the corresponding
HTG trimmer) for a period of 15 minutes. The speed of the
fan and therefore the output of the boiler is determined by
the temperature of the water sensed by the flow tempera-
ture sensor, consequently a high temperature at the flow
sensor results in a lower fan speed. As the water tempe-
rature increases, the temperature sensors – located on
the flow pipe of the boiler – reduce the fan speed via the
electronic circuitry. Depending on the load, either the water
temperature will continue to rise until the set point is
achieved or the water temperature will fall whereby fan
speed will increase relative to the output required. When
the boiler has reached the set point (+ hysterisis), the
burner will switch off. The built-in anti-cycle device prevents
the burner from re-lighting for approximately 5-minutes.
When the temperature of the flow sensor falls below the
set point (- hysterisis), the burner will re-light.

NOTE

If the spark/sensing electrode does not sense ignition the
appliance will re-attempt ignition a further 4-times then go
to lockout. When the set-point has been reached (the
position of the heating temperature selector) as measured
at the primary thermistor, the appliance will begin the
modulation phase whereby the fan and gas valve will
continuously modulate to maintain the set-point.
If the temperature continues to rise and exceeds the set-
point by 2°C (hysterisis), the burner will shut down. A new
ignition sequence will be enabled when the 5- minute anti-
cycle has been performed and the temperature at the
primary thermistor has dropped 8°C (hysterisis) below the
set-point.

NOTES

When the request for heating and/or hot water has been
satisfied, the appliance pump and fan may continue to
circulate to dissipate any residual heat within the appliance.

OR

OR

Содержание Mynute VHE

Страница 1: ...INSTRUCTIONS TO BE RETAINED BY USER Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic hot water systems in the UK My...

Страница 2: ...he system 17 5 4 Initial flushing of the system 17 5 5 Pre operation checks 17 5 6 Initiallighting 17 5 7 Checking gas pressure combustion analysis 17 5 8 Final flushing of the heating system 17 5 9 S...

Страница 3: ...chnical helpline for advice should you wish to use the Mynute VHE on a sealed pressurised system This booklet is an integral part of the appliance It is therefore necessary to ensure that the booklet...

Страница 4: ...e temperature selector clockwise to increase the boiler outlet temperature or counter clockwise to reduce the outlet flow temperature 2 digit LED display Displays the current outlet temperature of the...

Страница 5: ...cuitry to ensure flame stability at the burner Once successful ignition has been achieved the electronic circuit increases the gas rate to 75 for a period of 15 minutes Thereafter the boiler s output...

Страница 6: ...sumption Watts 75 Supply V Hz 230 50 Internal fuse 3 15A T for PCB 3 15A F for connections block External fuse 3A 2 7 Flue Details concentric 60 100 Maximum horizontal flue length 60 100mm 7 8m Maximu...

Страница 7: ...ternal external corner or boundary 300 mm I Above ground roof or balcony level 300 mm J From a surface or boundary facing the terminal 1200 mm K From a terminal facing a terminal 1200 mm L From an ope...

Страница 8: ...pes of a smaller size than the appliance gas inlet connection must not be used The installation must be tested for soundness in accordance with BS6891 If the gas supply serves more than one appliance...

Страница 9: ...um heat exchangers is used to protect the boiler and system from the effects of corrosion and or electrolytic action The inhibitor must be administered in strict accordance with the manufacturers inst...

Страница 10: ...tres The distance between the bottom of the F E tank and the highest point of the safety vent pipe must be no less than 500mm The supply of water to the F E tank should be taken from themainswatersupp...

Страница 11: ...people have access including balconies or flat roofs theterminalmustbeprotectedbyaguardofdurable material The guard must be fitted centrally over the terminal RefertoI S 813 whentheterminalis0 5metres...

Страница 12: ...e shall be unrestricted 3A 11 2 ALTERNATIVE CLOSE COUPLED ARRANGEMENT If necessary or if preferred a close coupled arrangement for the feed and expansion pipe work can be used as an alternative to a c...

Страница 13: ...Careshouldbe exercisedwhendeterminingthepositionoftheappliance with respect to hidden obstructions such as pipes cables etc When the position of the appliance has been decided using the template supp...

Страница 14: ...Connect the required number of flue extensions or bends up to the maximum equivalent flue length to the flue terminal see fig 7 8 The flue system should have a minimum of 1 maximum of3 risefromtheboil...

Страница 15: ...17mm per 1000mm NOTE When cutting an extension to the required length you must ensure that the excess is cut from the plain end of the extension see fig 8 Remove any burrs and check that any seals ar...

Страница 16: ...verter box ensuring that the exhaust pipe connects to theexhaustconnectionontheconcentrictotwinconverter Ifnecessarycuttheplainends male ofthetwinfluepipes to allow connection to the concentric to twi...

Страница 17: ...ions 4 6 3 CONDENSE PIPE During normal operation the boiler produces condense which is collected in a trap located in the lower part of the boiler A flexible pipe condense outlet pipe is connected to...

Страница 18: ...wiringdiagrams in section 8 for more detailed information 4 7 3 CONNECTINGTHE MAINS 230V INPUT fig 16 Locateandremovethescrewssecuringtheterminalblock cover 230V Pass the supply cable through the cabl...

Страница 19: ...properly filled and vented Ensure the flue system has been fitted properly and in accordance with the instructions 5 6 INITIAL LIGHTING Ensure the electrical supply to the appliance is switched on En...

Страница 20: ...user Failure to install and commission the appliance to the manufacturers instructions may invalidate the warranty 5 12 INSTRUCTINGTHE USER Hand over all documentation supplied with this appliance inc...

Страница 21: ...ssary the condense trap to ensurecorrectoperation 6 3 REPLACEMENTOFCOMPONENTS Althoughitisanticipatedthatthisappliancewillgiveyears ofreliable troublefreeservice thelifespanofcomponents willbedetermin...

Страница 22: ...NESS CHECK MUST BE CARRIEDOUT 6 11 ELECTRODES CONDENSE SENSOR fig 22 Carry out component removal procedure as described in 6 4 Unclip and remove the air chamber front and RH side covers Disconnect the...

Страница 23: ...bly A locateand remove the 3 external nuts B Replace in the reverse order Ensure all seals are in good condition taking care to ensure they are replaced correctly C Fig 27 A B B A Fig 28 6 15 CONDENSE...

Страница 24: ...wherebyonlythepump will run for 15 seconds then off for 15 seconds and will not fire until this period has elapsed 7 2 3 HEATING MODE WiththeselectorswitchintheONpositionandanyadditional controls time...

Страница 25: ...dswitchtheboilertotheOFFmode To adjust the gas valve you must first ensure that the fan Fig 30 Maximum screw Minimum screw Compensation pipe connection 7 4 2 GAS VALVE MINIMUM SETTING Locate and gentl...

Страница 26: ...mp 0 C 75 CO function time 15 min Flow NTC max temp 0 C 87 High limit thermostat 0 C 97 Burner thermostat 0 C 170 Maximum differential 0 C 35 IGNITION CONTROL VALUE Ignition attempts before L O lockou...

Страница 27: ...verted Final Reset check pump ensure there is sufficient return sensor temperature higher than circulation around heating circuit s thermistors flowsensor temperature AL34 Fan tacho signal fault Final...

Страница 28: ...e channel voltage free time clocks Programmableroomthermostats Externaltwin channelprogrammers Theappliancecan be used in conjunction with typical S Plan Y Plan systems see 8 4 1 8 4 2 please contact...

Страница 29: ...ormer FS Flow thermistor NTC RS Return thermistor NTC AD02A Main PCB CN1 CN5 Connection to PCB high voltage X4 X9 Connection to PCB low voltage F O H T Flow over heat thermostat H E T Heat exchanger t...

Страница 30: ...28 FUNCTIONALDIAGRAM 8 4 1 S Plan with Vokera 2 channel programmer 8 4 2 Y Plan with Vokera 2 channel programmer Fig 33 Fig 34 N L E...

Страница 31: ...E 1 Frame assembly 01005496 18 Cover assembly 10028554 20 Printed circuit board 10029717 21 Led light guide 10028557 26 Instrumental panel 10028551 27 Knob assembly 10028559 31 Case Assembly 01005497...

Страница 32: ...30 Table 2 200 27 200 27 200 580 200 580 36 25 200 200 POS DESCRIPTION 20VHE 25 Pipe 10029590 27 Pipe 10029592 36 Pipe 10029591 200 Washer 5023 580 Connection M 3 4 3 4 10029526...

Страница 33: ...267 9 Pipe 10029515 17 Air venting plug 10029306 25 Siphon 10028405 26 Flexible pipe 10028540 27 Flexible pipe 10027192 71 Pipe 10028430 72 Drain tap 01005137 73 Cock 10028431 247 Washer 5203 476 O ri...

Страница 34: ...de 10027864 6 Condense electrode 10026316 12 Gas pipe 10029607 13 Gas valve 10028538 15 3 4 gas cock 10020897 16 Cover for air box 10028345 19 Glass stopper assembly 10026328 27 Plug 10023805 35 Air g...

Страница 35: ...exchanger assembly 01005443 7 Conveyor 10028536 12 Flue drain connection 10028421 475 Washer 125 10026323 482 Washer 10026366 487 Washer 60 10026345 509 High limit thermostat 10026982 552 Washer 60 10...

Страница 36: ...Maximumgasrate 1 55 kg hr Minimumgasrate 0 39 kg hr Injectorsize 3 6 mm Efficiency SEDBUK 92 6 Band A Emissions CO max mg kWh 215 0 mg kWh CO min mg kWh 10 8 mg kWh NOx max mg kWh 97 1 mg kWh NOx min...

Страница 37: ...appliance data badge 10 7 1 CHECKING ADJUSTINGTHEAPPLIANCEFAN SPEEDS Move the selector switch to the OFF position and remove the 3 selector knobs 10 7 2 ABSOLUTE MAX FAN SPEED LocatetheMAXtrimmer fig...

Страница 38: ...HAT TYPE OF SCALE REDUCER HAS BEEN FITTED FOR THE DOMESTIC HOT WATER MODE MEASURE RECORD GAS RATE 3 hr MAXIMUM BURNER OPERATING PRESSURE IF APPLICABLE mbar COLD WATER INLET TEMPERATURE C HOT WATER OUT...

Страница 39: ...CARD SERIAL No COMMENTS SIGNATURE SERVICE 3 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No COMMENTS SIGNATURE SERVICE 4 DATE ENGINEER NAME COMPANY NAME TEL No CORGI ID CARD SERIAL No...

Страница 40: ...es vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 099 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited reserve the...

Отзывы: