6

SECTION 3  GENERAL REQUIREMENTS (UK)

BS 5440

BS 5440

BS 5449

BS 6798

BS 6891

PART 1

PART 2

PART 1

 

 FLUES

 FLUES & VENTILATION

FORCED CIRCULATION HOT WATER SYSTEMS

INSTALLATION OF BOILERS OF RATED INPUT NOT EXCEEDING 60kW

  LOW PRESSURE INSTALLATION PIPES

This appliance must be installed by a competent person 
in accordance with the Gas Safety (Installation & Use) 
Regulations.

3.1 RELATED DOCUMENTS

The installation of this boiler must be in accordance with 
the relevant requirements of the Gas Safety (Installation 
& Use) Regulations, the local building regulations, the 
current I.E.E. wiring regulations, the bylaws of the local 
water undertaking, the Building Standards (Scotland) 
Regulation, and Building Standards (Northern Ireland) 
Regulations.
It should be in accordance also with any relevant re-
quirements of the local authority and the relevant rec-
ommendations of the following British Standard Codes 
of Practice.

3.2 LOCATION OF APPLIANCE

The appliance may be installed in any room or internal 
space, although particular attention is drawn to the re-
quirements of the current I.E.E. wiring regulations, and in 
Scotland, the electrical provisions of the Building Regula-
tions, with respect to the installation of the appliance in 
a room or internal space containing a bath or shower.

When an appliance is installed in a room or internal space 
containing a bath or shower, the appliance or any control 
pertaining to it must not be within reach of a person using 
the bath or shower.

The location chosen for the appliance must permit the 
provision of a safe and satisfactory fl ue and termination.  
The location must also permit an adequate air supply for 
combustion purposes and an adequate space for servic-
ing and air circulation around the appliance.  Where the 
installation of the appliance will be in an unusual location 
special procedures may be
Necessary, BS 6798 gives detailed guidance on this 
aspect.

A compartment used to enclose the appliance must be 
designed and constructed specifi cally for this purpose.  An 
existing compartment/cupboard may be utilised provided 
that it is modifi ed to suit.

Details of essential features of compartment/cupboard 
design including airing cupboard installations are given 
in BS 6798.  This appliance is not suitable for external 
installation.

3.3 GAS SUPPLY

The gas meter – as supplied by the gas supplier – must 
be checked to ensure that it is of adequate size to deal 
with the maximum rated input of all the appliances that 
it serves.  Installation pipes must be fi tted in accordance 

with BS 6891.
Pipe work from the meter to the appliance must be of 
adequate size.  Pipes of a smaller size than the appliance 
gas inlet connection must not be used.  The installation 
must be tested for soundness in accordance with BS6891.
If the gas supply serves more than one appliance, it must 
be ensured that an adequate supply is maintained to 
each appliance when they are in use at the same time.

3.4 FLUE SYSTEM

The terminal should be located where the dispersal of 
combustion products is not impeded and with due regard 
for the damage and discoloration that may occur to build-
ing products located nearby.  The terminal must not be 
located in a place where it is likely to cause a nuisance 
(see fi g. 4).
In cold and/or humid weather, water vapour will condense 
on leaving the terminal; the effect of such pluming must 
be considered.
If installed less than 2m above a pavement or platform 
to which people have access (including balconies or 
fl at roofs) the terminal must be protected by a guard of 
durable material.  The guard must be fi tted centrally over 
the terminal.  

Refer to BS 5440 Part 1, when the terminal is 0.5 metres 
(or less) below plastic guttering or 1 metre (or less) below 
painted eaves. metres (or less) below plastic guttering or 
1 metre (or less) below painted eaves.

3.5 AIR SUPPLY

The following notes are intended for general guidance only.
This appliance is a room-sealed, fan-fl ued boiler, conse-
quently it does not require a 
Permanent air vent for combustion air supply.
When installed in a cupboard or compartment, ventilation 
for cooling purposes is also not required.

3.6 WATER CIRCULATION

Detailed recommendations are given in BS 5449 Part 1 
and BS 6798.  The following notes are for general guid-
ance only.

3.6.1 PIPEWORK

It is recommended that copper tubing to BS 2871 Part 
1 is used in conjunction with soldered capillary joints.
Where possible pipes should have a gradient to ensure 
air is carried naturally to air release points and that water 
fl ows naturally to drain cocks.

Except where providing useful heat, pipes should be 
insulated to avoid heat loss and in particular to avoid the 
possibility of freezing.  Particular attention should be paid 
to pipes passing through ventilated areas such as under 
fl oors, loft space, and void areas.

Содержание MYNUTE 15 VHE

Страница 1: ...TO BE RETAINED BY USER Mynute VHE High efficiency open vent boiler Vok ra is a licensed member of the Benchmark scheme which aims to improve the standards of installation and commissioning of domestic...

Страница 2: ...5 3 Initial filling of the system 18 5 4 Initial flushing of the system 18 5 5 Pre operation checks 18 5 6 Initial lighting 18 5 7 Checking gas pressure combustion analysis 18 5 8 Final flushing of th...

Страница 3: ...voltage directive 2006 95 EC Directive 2009 125 EC Ecodesign for energy using ap pliances Directive 2010 30 EU Indication by labelling of the con sumption of energy by energy related products Delegate...

Страница 4: ...e temperature selector clockwise to increase the boiler outlet temperature or counter clockwise to reduce the outlet flow temperature 2 digit LED display Displays the current outlet temperature of the...

Страница 5: ...sure flame stability at the burner Once successful ignition has been achieved the electronic circuitry increases the gas rate to 75 for a period of 15 minutes Thereafter the boiler s output will eithe...

Страница 6: ...50mm from casing or 25mm above flue elbow whichever is applicable Bottom 150mm Front 600mm 2 5 Connections Flow return 22mm Gas 15mm Condense 21mm 2 6 Electrical Power consumption Watts 35 Supply V Hz...

Страница 7: ...ed 15 kW Seasonal space heating energy efficiency s 93 For boiler space heaters and boiler combination heaters useful heat output For boiler space heaters and boiler combination heaters useful efficie...

Страница 8: ...3 GAS SUPPLY The gas meter as supplied by the gas supplier must be checked to ensure that it is of adequate size to deal with the maximum rated input of all the appliances that it serves Installation...

Страница 9: ...ins electricity supply must allow for complete isolation from the supply The preferred method is by using a double pole switch with a contact separation of at least 3mm The switch must only supply the...

Страница 10: ...top of the boiler to the bottom of the F E tank shall be no less than 1 metre whilst the maximum distance shall be no greater than 30 metres The distance between the bottom of the F E tank and the hi...

Страница 11: ...ther watervapourwillcondense on leaving the terminal the effect of such pluming must be considered If installed less than 2m above a pavement or platform to which people have access including balconie...

Страница 12: ...he combined feed and vent pipe shall be unrestricted 3A 11 2 ALTERNATIVE CLOSE COUPLED ARRANGEMENT If necessary or if preferred a close coupled arrange ment for the feed and expansion pipe work can be...

Страница 13: ...if applicable 4 5 FITTING THE FLUE The top flue outlet permits both horizontal and vertical flue applications to be considered alternatively the Vokera twin flue system can be utilised if longer flue...

Страница 14: ...d an appropriate type and quantity of fixing should be used to ensure that the bracket is mounted securely Once the bracket has been secured to the wall attach the rear flue terminal to the appliance...

Страница 15: ...730mm 208mm Using the dimensions given in fig 12 as a reference mark and cut a 115mm hole in the ceiling and or roof X X 139 mm Fit the appropriate flashing plate to the roof and insert the vertical...

Страница 16: ...be given to the fact that there is the possibility of a small amount of condensate dripping from the terminal Ensure that the entire flue system is adequately sup ported use at least one bracket for...

Страница 17: ...centric to twin converter The last twin flue pipes must be pushed 50mm onto the male spigots of the concentric to twin converter You must ensure that the entire flue system is properly supported and c...

Страница 18: ...iled instructions ANY EXTERNAL CONTROL OR WIRING MUST BE SERVED FROMTHE SAME ISOLATOR AS THAT OF THE APPLIANCE The supply cable from the isolator to the appliance must be 3 core flexible sized 0 75mm...

Страница 19: ...fig 21 Pass the pump cable first through the cable anchorage point and then through the cable glands Connect the pump cable wires LIVE NEUTRAL EARTH to their corresponding terminals Live brown Neutral...

Страница 20: ...e 7 8 particularly continuity polarity and resistance to earth Ensure the 3 AMP fuse supplied with the appliance has been fitted Ensure the system has been properly filled and vented Ensure the flue s...

Страница 21: ...ECURED ENSURE ALL PIPE WORK IS RE CHECKED FOR TIGHTNESS RE FIT APPLIANCE CASING COMPLETE BENCHMARK CHECKLIST FOR UK ONLY Complete details of the boiler controls installation and commissioning in the B...

Страница 22: ...pliancedesignspecifica tion Anydeteriorationinperformancemustbeidentified and rectified without delay Check that the burner and main heat exchanger are clean and free from any debris or obstruction Ch...

Страница 23: ...e unit Disconnect the electrical plug and leads from the gas valve slacken and unscrew gas valve inlet and outlet connections Please note the sealing washers A must be discarded and replaced with new...

Страница 24: ...cations Step 4 fig 29 Locate and remove the 3 nuts B that secure the fan flue assembly to the heat exchanger The fan flue assembly can now be removed with care Step 5 The burner can now be removed wit...

Страница 25: ...he appliance ease the control panel from its location Step 2 Disconnect all wiring connections from the flue fan as sembly and heat exchanger Step 3 Slacken the gas pipe A at the outlet connection and...

Страница 26: ...epumpwillrunfor15 secondsthenofffor15 seconds and will not fire until this period has elapsed 7 2 3 HEATING MODE With the selector switch in the ON position and any additional controls time clock prog...

Страница 27: ...G Locate and gently turn the HTG trimmer till the minimum value fan speed is obtained and check that it corre sponds with the appropriate CO2 value Minimum for the respective appliance If the CO2 read...

Страница 28: ...nce terminal strip fig 21 NOTE Should it be found that the fuse has failed but no fault is indicated a detailed continuity check will be required to trace the fault A visual inspection of components m...

Страница 29: ...uity If the boiler still fails to respond refer to the detailed faultfinding flowcharts located at the end of this section CODE CAUSE ALARM TYPE ACTION AL10 Ignition failure not flame sensed con dense...

Страница 30: ...YPICAL CONTROL APPLICATIONS The appliance can be used with the following controls Single channel voltage free time clocks Programmable room thermostats Externaltwin channelprogrammers Theappliancecan...

Страница 31: ...nsformer FS Flow thermistor NTC RS Return thermistor NTC AD02X Main PCB CN1 CN5 Connection to PCB high voltage X4 X9 Connection to PCB low voltage F O H T Flow over heat thermostat H E T Heat exchange...

Страница 32: ...30 FUNCTIONAL DIAGRAM 8 4 1 S Plan with Vokera 2 channel programmer 8 4 2 Y Plan with Vokera 2 channel programmer Fig 40 Fig 41 N L E...

Страница 33: ...he meter must be purged and checked for gas soundness 10 6 CORRECTING THE CO2 VALUES ADJUSTING THE GAS VALVE THE GAS VALVE MUST BE SET UP OR ADJUSTED WITHTHE AID OF A PROPERLY CALIBRATED FLUE GAS ANAL...

Страница 34: ...If different adjust the gas valve according to the above 10 8 APPLIANCE FAN SPEEDS The appliance fan speeds require to be checked and or adjusted prior to making any adjustments to the gas valve or i...

Страница 35: ...tabilise YES Is CO less than 350ppm AND CO CO2 ra o less than 0 004 NO Boiler is opera ng sa sfactorily No further ac ons required Ensure test points are capped boiler case is correctly replaced and a...

Страница 36: ...FRPPLVVLRQLQJ FKHFNOLVW completed in full 7R LQVWLJDWH WKH ERLOHU JXDUDQWHH WKH ERLOHU QHHGV WR EH UHJLVWHUHG ZLWK WKH PDQXIDFWXUHU ZLWKLQ RQH PRQWK RI WKH LQVWDOODWLRQ 7R PDLQWDLQ WKH ERLOHU JXDUDQW...

Страница 37: ...HU LQWHUORFN 3URYLGHG ALL SYSTEMS 7KH V VWHP KDV EHHQ XVKHG DQG FOHDQHG LQ DFFRUGDQFH ZLWK 6 DQG ERLOHU PDQXIDFWXUHU V LQVWUXFWLRQV Yes KDW V VWHP FOHDQHU ZDV XVHG KDW LQKLELWRU ZDV XVHG 4XDQWLW OLWUH...

Страница 38: ...SKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UDWH 2 SSP AND 2 W PLQ UDWH KHUH 3RVVLEOH 2 SSP AND 2 RPPHQWV 6LJQDWXUH SERVICE 04 DWH QJLQHHU QDPH RPSDQ QDPH 7HOHSKRQH 1R DV VDIH UHJLVWHU 1R 5HFRUG W PD UDW...

Страница 39: ...37...

Страница 40: ...38...

Страница 41: ......

Страница 42: ...1HG enquiries vokera co uk www vokera co uk www vokera ie Sales General Enquires T 0844 391 0999 F 0844 391 0998 Vok ra Ireland West Court Callan Co Kilkenny T 056 7755057 F 056 7755060 Vok ra Limited...

Отзывы: