A-2
Table 16: Power Monitor Parameters
Parameter (Description, units)
Min.
Max.
Default
Recommended Settings
Line Side Voltage (Nominal Voltage, volts)
90
650
208
Supply voltage
Over Voltage (tolerance, %)
6
18
12
10
Under Voltage (tolerance, %)
6
18
12
10
Phase Unbalance (%)
2
25
6
5
Lockout Time (Delay on Break, seconds)
0.1
25
0.5
120
Delay Time (Delay on Make, seconds)
0
30
0
0
Response Time (Delay on Fault, seconds)
0.1
20
2
2
Control Mode (none)
Off / Auto / On
Auto
On
Contactor Test (Volt Diff)
OFF
5
OFF
OFF
Adjustment of Parameters in Order of Display
The following describes how to adjust the power monitor parameters in order of display if adjustment is
needed.
•
Line Voltage
—
This gives an active display of the line voltage to the machine. By default, this is the
normal display.
•
Load Side Voltage
—
If connected, this provides an active display of the load side voltage in the machine.
•
Voltage Setpoint
(VAC Flashes)
—
Press the UP and DOWN arrows. This may be set to the normal
operating voltage of the device being protected. Adjustment increments are 1 volt.
•
Under/Over Voltage Tolerance
(UNDERVOLTAGE/OVERVOLTAGE Flashes)
—
Press the UP and DOWN
arrows. The tolerance is displayed in percentages.
•
Imbalance Voltage Tolerance
(% IMBALANCE Flashes)
—
This value may be adjusted by pressing the UP
and DOWN arrows.
•
Lockout Time
(SECONDS Flashes)
—
This value may be adjusted by pressing the UP and DOWN arrows.
This is the delay-on-break timer value.
•
Delay Time
(RESP. SECONDS Flashes)
—
This display shows time in seconds and tenths of seconds. This
value may be adjusted by pressing the UP and DOWN arrows. This is the time that a fault is allowed
before shutdown occurs.
•
Control Mode
(ON OFF AUTO Flashes)
—
This value may be adjusted to OFF (load will not turn on), ON
(load will turn on whenever no faults exist and timers are finished), and AUTO (load will turn on when a
control input is active).
•
Contactor Fault Monitor Mode
(CONTACTOR FAULT Flashes)
—
This option allows for monitoring of the
contactor and provides lock-out if the line voltage and load side voltage vary by more than five (5) volts.
Pressing the UP or DOWN arrow will toggle between OFF (default) and ON. The load side of the
contactor must be connected to the load terminals of the power monitor to use this option.
•
Display of Fault Memories
(MEM Flashes)
—
Pressing UP or DOWN arrow displays the last fault
conditions that shut down the machine. The first 25 faults are recorded. The top number displayed
represents the fault memory. The middle number represents the total number of faults that have
occurred since the fault memory was cleared. To clear the memory, press and hold both the UP and
DOWN arrows until the display is cleared.
Содержание Tube-Ice HFO10
Страница 2: ......
Страница 6: ......
Страница 10: ......
Страница 12: ......
Страница 16: ...2 4 Figure 3 Water Cooled Piping Schematic ...
Страница 17: ...2 5 Figure 4 Air Cooled Piping Schematic ...
Страница 36: ......
Страница 40: ......
Страница 43: ...6 3 Figure 16 Panel Layout 60 Hz Non CE Machines ...
Страница 44: ...6 4 Figure 17 Electrical Schematic Control Circuit All Voltages 50 Hz ...
Страница 45: ...6 5 Figure 18 Electrical Schematic Control Circuit All Voltages 60 Hz ...
Страница 46: ...6 6 Figure 19 Electrical Schematic 3 Phase Power All Voltages 50 Hz ...
Страница 47: ...6 7 Figure 20 Electrical Schematic 3 Phase Power All Voltages 60 Hz ...
Страница 68: ......
Страница 96: ......
Страница 110: ...Notes ...
Страница 111: ...Notes ...