05TA Service Manual
INSTALLING YOUR TUBE-ICE
®
MACHINE
8/13/01
3-10
CONDENSER EQUIVALENT LINE SIZE WORKSHEET
Discharge Gas Line O.D. ___________________
Fitting Type
Number Used
Factor
Total
Globe Valve (open)
Angle Valve (open)
90
°
Elbow
45
°
Elbow
Tee
Feet of Straight Copper Used
Total Fitting Factor
Total Equivalent Feet
Copper Tubing Type “L”
1 1/8” O.D.
1 3/8” O.D.
1 5/8” O.D.
2 1/8” O.D.
Globe valve (open)
28
36
42
57
Angle valve (open)
15
18
21
28
90
o
Elbow
3
4
4
5
45
o
Elbow
1.5
2
2
2.5
Tee (90
°
turn through)
6
8
9
12
Tee (straight through)
2
2.5
2.8
3.5
TABLE 3-5
Equivalent Feet Due To Friction
FIGURE 3-6
Minimum Traps For Discharge Lines
*Note: Each recommended line size is based on use of Type “L” copper tubing at a maximum
equivalent distance of 150 feet. See TABLE 3-5 for equivalent feet of valves and fittings.
Содержание TUBE-ICE 05TA
Страница 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Страница 46: ...05TA Service Manual ELECTRICAL CONTROLS 8 13 01 6 4 FIGURE 6 2 Electrical Schematic All Voltages 50 60 Hz ...
Страница 82: ...05TA Service Manual SERVICE OPERATIONS 8 13 01 9 18 FIGURE 9 10 Cutter Drive Parts ...
Страница 83: ...05TA Service Manual SERVICE OPERATIONS 8 13 01 9 19 FIGURE 9 11 Cutter Parts crushed ice option ...
Страница 95: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 11 FIGURE 10 3 Control Panel Parts ...
Страница 97: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 13 FIGURE 10 4 Wiring Schematic ...
Страница 103: ...05TA Service Manual TABLES CHARTS 8 14 01 11 1 11 Tables Charts ...
Страница 111: ...05TA Service Manual INDEX 8 13 01 12 4 ...