05TA Service Manual
TABLES & CHARTS
8/14/01
11-2
05TA SPECIFICATIONS, 208-230 Volt-3 Phase- 60Hz
Tube Size
inches
(cm)
1
(2.54)
1 1/4
(3.17)
1 1/2
(3.18)
Nominal Capacity
(1)
lbs/day
(Kg/day)
11,000
(4,990)
10,000
(4,536)
9,500
(4,309)
Overall Dimensions (LxWxH)
inches
(meters)
60 x 32 x 84
(1.5x0.81x2.1)
60 x 32 x 84
(1.5x0.81x2.1)
60 x 32 x 84
(1.5x0.81x2.1)
Shipping Weight
lbs
(Kg)
3200
(1452)
3200
(1452)
3200
(1452)
Operating Weight
lbs
(Kg)
2975
(1349)
2975
(1349)
2975
(1349)
Refrigerant Charge (HCFC-22)
lbs
(Kg)
260
(118)
260
(118)
260
(118)
Total FLA Water Cooled
(2)
66.9
66.9
66.9
Total FLA Air Cooled
(2)
79.4
79.4
79.4
Maximum Fuse
WC / AC
145/155
145/155
145/155
Minimum Ampacity
WC / AC
81.8/94.3
81.8/94.3
81.8/94.3
Compressor -HP/KW/FLA
15/11.2/59.6
15/11.2/59.6
15/11.2/59.6
Water Pump -HP/KW/FLA
1.5 / 1.9 / 4.8
1.5 / 1.9 / 4.8
1.5 / 1.9 / 4.8
Cutter Motor -HP/KW/FLA
0.5 / 0.7 / 1.9
0.5 / 0.7 / 1.9
0.5 / 0.7 / 1.9
THR
Btu/hr
(kW)
170,000
(49.8)
170,000
(49.8)
170,000
(49.8)
Water Requirements
-makeup
(3)
gpm
(m
3
/ Hr)
1.2
(0.27)
1.2
(0.27)
1.2
(0.27)
-condenser
(4)
gpm
(m
3
/ Hr)
37
(8.40)
37
(8.40)
37
(8.40)
Connection Sizes
-makeup water
FPT
3/4”
3/4”
3/4”
-tank drain
FPT
1”
1”
1”
-condenser water inlet
FPT
1 1/4”
1 1/4”
1 1/4”
-condenser water outlet
MPT
1 1/4”
1 1/4”
1 1/4”
-AC condenser inlet
ODC
1 5/8”
1 5/8”
1 5/8”
-AC condenser outlet
ODC
1 1/8”
1 1/8”
1 1/8”
Marley Cooling Tower
(5)
4821
4821
4821
-dimensions (LxWxH)
ft
(meters)
5x 4 x 6.5
(1.5x1.2x2.0)
5x 4 x 6.5
(1.5x1.2x2.0)
5x 4 x 6.5
(1.5x1.2x2.0)
-shipping weight
lbs
(Kg)
740
(336)
740
(336)
740
(336)
-operating weight
lbs
(Kg)
1340
(
608)
1340
(
608)
1340
(
608)
-fan (HP/KW/FLA)
1 / 0.8 / 3.6
1 / 0.8 / 3.6
1 / 0.8 / 3.6
Tower Pump
-flow
gpm
(m
3
/Hr)
78
(17.7)
78
(17.7)
78
(17.7)
-TDH
minimum
ft
(m)
80
(24.4)
80
(24.4)
80
(24.4)
-HP/KW/FLA
3 /2.2 / 9.6
3 /2.2 / 9.6
3 /2.2 / 9.6
-connections (inlet x outlet)
FPT
1.5” x 1”
1.5” x 1”
1.5” x 1”
-shipping weight
lbs
(Kg)
65
(29.5)
65
(29.5)
65
(29.5)
Kramer Air-Cooled Condenser
(6)
DD-311
DD-311
DD-311
- # of Fans / HP
5 / 0.5
5 / 0.5
5 / 0.5
-total KW/FLA
2.8/ 9.0
2.8 / 9.0
2.8 / 9.0
-inlet connection
ODC
1 5/8”
1 5/8”
1 5/8”
-outlet connection
ODC
1 1/8”
1 1/8”
1 1/8”
-shipping weight
lbs
(Kg)
610
(277)
610
(277)
610
(277)
-operating weight
lbs
(Kg)
660
(299)
660
(299)
660
(299)
(1) Nominal capacity is based on 70°F makeup water, 100°F condensing temperature, 70°F ambient, and 0% blowdown.
(2) FLA for 460 volt models is approximately 1/2 that of 230 volt models. Total FLA does not include cooling tower.
(3) Makeup water is maximum value and includes 10 gallons per cycle blowdown.
(4) Condenser flow rate is for 85°F entering water temperature and 100°F condensing.
(5) Tower sized for 80°F wet bulb temperature.
(6) Recommended air-cooled condenser is based on 15°F TD.
Vogt reserves the right to change designs and specifications without notice.
Table 11-1
Содержание TUBE-ICE 05TA
Страница 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M06 05TA Model ...
Страница 46: ...05TA Service Manual ELECTRICAL CONTROLS 8 13 01 6 4 FIGURE 6 2 Electrical Schematic All Voltages 50 60 Hz ...
Страница 82: ...05TA Service Manual SERVICE OPERATIONS 8 13 01 9 18 FIGURE 9 10 Cutter Drive Parts ...
Страница 83: ...05TA Service Manual SERVICE OPERATIONS 8 13 01 9 19 FIGURE 9 11 Cutter Parts crushed ice option ...
Страница 95: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 11 FIGURE 10 3 Control Panel Parts ...
Страница 97: ...05TA Service Manual OPTIONS AND ACCESSORIES 8 13 01 10 13 FIGURE 10 4 Wiring Schematic ...
Страница 103: ...05TA Service Manual TABLES CHARTS 8 14 01 11 1 11 Tables Charts ...
Страница 111: ...05TA Service Manual INDEX 8 13 01 12 4 ...