10TA Service Manual
SERVICE OPERATIONS
4/28/14
9-9
Sentronic Oil Pressure Safety Control
(4D & 6D compressors before March 2011).
The Sentronic utilizes a pressure sensor and an electronic control module to precisely measure oil
pump differential pressure. The main advantage of Sentronic is the elimination of the traditional
capillary tubes, bellows, and pressure connections that mechanical pressure switches require to
measure differential oil pressure. These require careful handling and are known to be a source of
leaks in refrigeration systems.
A second advantage of Sentronic is in the use of a precise electronic clock for the two-minute time
out circuit. Traditional mechanical controls use resistance heaters to provide the time to trip in the
event of low oil pressure. 208 volt systems, low ambient temperatures or brown-out type conditions
cause the heater output to be reduced, thus increasing the time out period from two minutes to three
or four minutes when low oil pressure conditions exist. With the electronic clock, the time out will
always be the same.
As a result of the elimination of the capillary tube measuring system and a more precise timing
circuit, Sentronic will improve the overall reliability of the refrigeration system. As in the past, all
new and replacement Copelametic compressors equipped with oil pumps require the use of a
Copeland approved oil pressure safety switch. Failure to use an approved oil pressure safety switch
will be considered as misuse of the compressor, and can adversely affect warranty replacement of
the compressor should a lubrication connected failure occur.
FIGURE 9-7A
Sentronic Oil Pressure Safety Control
Sentronic Sensor
(2D, 3D, 4D & 6D compressors before March 2011). The same oil pressure
sensor is used for all Sentronic Oil Pressure Controls. It mounts directly into the oil pump. The
sensor measures oil pump differential pressure. It has an internal contact that opens on low oil
pressure and signals the Sentronic electronic control module to begin time out. The same contact
closes when proper oil pressure is present and stops the module time out. Should oil pressure fall
below 7-9 PSID for a period of two minutes, the Sentronic module will open the control circuit,
using its Normally-Closed (N) contact, and shut the compressor off.
Approximate oil pressure can be measured in the field. Oil pumps are furnished with a Schrader
valve mounted on the oil pump discharge port. To measure oil pressure, subtract crankcase
pressure from discharge oil pressure. Tripping of the oil pressure safety switch is a warning that
the system has been without proper lubrication for too long a time. Repeated trips of the oil
pressure safety control are a clear indication that something in the system requires immediate
remedial action.
Sentronic Oil Safety (Sensor Only)
Part #:
Sentronic Oil Safety Control
(Entire Unit)
Part #:
Содержание P18FXT
Страница 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M08 10TA Model ...
Страница 10: ...10TA Service Manual TABLE OF CONTENTS vi BLANK ...
Страница 20: ...10TA Service Manual INTRODUCTION 4 14 14 1 10 BLANK ...
Страница 40: ...10TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 4 14 14 3 18 BLANK PAGE ...
Страница 43: ...10TA Service Manual HOW YOUR TUBE ICE MACHINE WORKS 4 14 2014 4 3 FIGURE 4 1 Water Cooled Piping Schematic ...
Страница 44: ...10TA Service Manual HOW YOUR TUBE ICE MACHINE WORKS 4 14 2014 4 4 FIGURE 4 2 Air Cooled Piping Schematic ...
Страница 50: ...10TA Service Manual START UP AND OPERATION 4 14 14 5 6 BLANK ...
Страница 51: ...10TA Service Manual ELECTRICAL CONTROLS 4 14 14 6 1 6 Electrical Controls FIGURE 6 1 Control Panel SS PB1 PB2 ...
Страница 52: ...10TA Service Manual ELECTRICAL CONTROLS 4 14 14 6 2 FIGURE 6 2 Control Panel Components Standard ...
Страница 60: ...10TA Service Manual ELECTRICAL CONTROLS 4 14 14 6 10 BLANK ...
Страница 111: ...10TA Service Manual 10 7 OPTIONS AND ACCESSORIES FIGURE 10 4 Wiring Schematic Mid Size Machine P112 P118 P18XT ...
Страница 112: ...10 8 10TA Service Manual OPTIONS AND ACCESSORIES BLANK ...
Страница 120: ...10TA Service Manual TABLES CHARTS 7 2 14 11 8 BLANK ...
Страница 124: ...10TA Service Manual INDEX 5 30 14 12 4 ...