10TA Service Manual
INSTALLING YOUR TUBE-ICE
®
MACHINE
4/14/14
3-8
14.
When extreme cold conditions are expected or encountered (temperatures below 0
°
F and wind
greater than 15 MPH), it may be necessary to install a protective enclosure around the condenser.
Apparatuses such as louvers may also be used for varying conditions. Contact the factory for
suggestions.
15.
After installation, the field installed lines are to be evacuated to a vacuum of 500 microns or less
and held for at least one hour. After the vacuum pump is removed, vacuum should hold at 500
microns or less for at least 5 minutes.
16.
The machine is shipped with a full operating charge of refrigerant sufficient to fill the condenser
and connecting lines. If the condenser piping is longer than 50 feet (one way), additional R-22
or R-404A may need to be added to retain enough refrigerant in the receiver for thawing
purposes (see table. Refer to the operating level mark on the receiver and charge accordingly.
Each 1” of liquid level in the receiver equals approximately 5.5 pounds of R-22 or R-404a.
Liquid Line Size
75 ft.
100 ft.
125 ft.
150 ft.
1/2”
none
None
None
2
5/8”
none
2
4
6
7/8”
none
4
8
12
1-1/8”
none
6
12
18
TABLE 3-3
Pounds of R-22 /R404A to Add vs. Liquid Line Length
17.
All piping must be done in accordance with applicable local and national codes. Such codes may
include “The Safety Code For Mechanical Refrigeration” (ANSI B9.1) and “The Code For
Refrigerant Piping” (ANSI B31.5).
18.
The following installation guidelines are strongly suggested. While they do not affect the
machine warranty, they may be required for safe operation and to comply with all applicable
electrical and mechanical codes:
a. Local electrical code must be checked for wiring method.
b. The installer must provide a disconnect switch(s) adjacent to the condenser.
c. Electrical connections between the condenser and the Tube-Ice
®
machine require
minimum 10 ga. wire for 200/230V motors / 14 ga. wire for 400/460V motors. For control
wiring, a minimum of 14 ga. wire should be used.
d. All electrical fittings and components exposed to the weather must be suitable for
outdoor installation.
The design total heat rejection for each Tube-Ice
®
machine, the recommended air-cooled condenser,
and condenser physical and electrical data are shown on the next page. Specified energy efficiency
ratings of the ice machines are based on use of the recommended condenser and approved piping
practices.
Recommended condensers provide the indicated total heat rejection at 90
°
F ambient, 100
°
F
condensing. Vogt Ice, LLC is not responsible for head pressure problems if other than the
recommended condensers are used. For continuous operation at ambient temperature above 105
°
F,
consult the factory about using a larger condenser.
Содержание P18FXT
Страница 4: ...Vogt Tube Ice Machines Installation Service Manual and Parts Catalog 12A4171M08 10TA Model ...
Страница 10: ...10TA Service Manual TABLE OF CONTENTS vi BLANK ...
Страница 20: ...10TA Service Manual INTRODUCTION 4 14 14 1 10 BLANK ...
Страница 40: ...10TA Service Manual INSTALLING YOUR TUBE ICE MACHINE 4 14 14 3 18 BLANK PAGE ...
Страница 43: ...10TA Service Manual HOW YOUR TUBE ICE MACHINE WORKS 4 14 2014 4 3 FIGURE 4 1 Water Cooled Piping Schematic ...
Страница 44: ...10TA Service Manual HOW YOUR TUBE ICE MACHINE WORKS 4 14 2014 4 4 FIGURE 4 2 Air Cooled Piping Schematic ...
Страница 50: ...10TA Service Manual START UP AND OPERATION 4 14 14 5 6 BLANK ...
Страница 51: ...10TA Service Manual ELECTRICAL CONTROLS 4 14 14 6 1 6 Electrical Controls FIGURE 6 1 Control Panel SS PB1 PB2 ...
Страница 52: ...10TA Service Manual ELECTRICAL CONTROLS 4 14 14 6 2 FIGURE 6 2 Control Panel Components Standard ...
Страница 60: ...10TA Service Manual ELECTRICAL CONTROLS 4 14 14 6 10 BLANK ...
Страница 111: ...10TA Service Manual 10 7 OPTIONS AND ACCESSORIES FIGURE 10 4 Wiring Schematic Mid Size Machine P112 P118 P18XT ...
Страница 112: ...10 8 10TA Service Manual OPTIONS AND ACCESSORIES BLANK ...
Страница 120: ...10TA Service Manual TABLES CHARTS 7 2 14 11 8 BLANK ...
Страница 124: ...10TA Service Manual INDEX 5 30 14 12 4 ...