5
LOCATING STOVE
36"
36"
CORNER CLEARANCES
Top View Minimum
Corner Clearances from
Combustible Surfaces
BACKWALL
COMBUSTIBLE
CONSTRUCTION
ACCORDING TO
NFPA 211
SIDEWALL
COMBUSTIBLE
CONSTRUCTION
ACCORDING TO
NFPA 211
DASHED LINE SHOWS
HORIZONTAL CHIMNEY
CONNECTOR AND
ADDITIONAL FLOOR
PROTECTION REQUIRED
FLOOR
PROTECTOR
(TOP VIEW)
(FRONT VIEW)
(SIDE VIEW)
CEILING
BACKWA
LL
SIDEWALL
CEILING
36”
36”
59”
18”
18”
18”
18”
FLOOR PROTECTOR
Minimum
Floor-to-ceiling
Height
8ft / 2.4m
18”
18”
36”
56”
36"
36"
CORNER CLEARANCES
Top View Minimum
Corner Clearances from
Combustible Surfaces
BACKWALL
COMBUSTIBLE
CONSTRUCTION
ACCORDING TO
NFPA 211
SIDEWALL
COMBUSTIBLE
CONSTRUCTION
ACCORDING TO
NFPA 211
DASHED LINE SHOWS
HORIZONTAL CHIMNEY
CONNECTOR AND
ADDITIONAL FLOOR
PROTECTION REQUIRED
FLOOR
PROTECTOR
(TOP VIEW)
(FRONT VIEW)
(SIDE VIEW)
CEILING
BACKWA
LL
SIDEWALL
CEILING
36”
36”
59”
18”
18”
18”
18”
FLOOR PROTECTOR
Minimum
Floor-to-ceiling
Height
8ft / 2.4m
18”
18”
36”
56”
36"
36"
CORNER CLEARANCES
Top View Minimum
Corner Clearances from
Combustible Surfaces
BACKWALL
COMBUSTIBLE
CONSTRUCTION
ACCORDING TO
NFPA 211
SIDEWALL
COMBUSTIBLE
CONSTRUCTION
ACCORDING TO
NFPA 211
DASHED LINE SHOWS
HORIZONTAL CHIMNEY
CONNECTOR AND
ADDITIONAL FLOOR
PROTECTION REQUIRED
FLOOR
PROTECTOR
(TOP VIEW)
(FRONT VIEW)
(SIDE VIEW)
CEILING
BACKWA
LL
SIDEWALL
CEILING
36”
36”
59”
18”
18”
18”
18”
FLOOR PROTECTOR
Minimum
Floor-to-ceiling
Height
8ft / 2.4m
18”
18”
36”
56”
Minimum Clearance Dimensions from Combustible Surfaces
Proper clearances must be maintained for adequate air circulation. Adequate ventilation must be provided
while operating this stove.
1. The stove must be placed on solid concrete, solid masonry, or when installed on a combustible floor a solid
surface floor protector listed to UL1618 Type 2 with a minimum of 1˝ thick and a R-value of 3.0 or greater must
be used, such as Hy-C or Imperial Model UL 5460BK. (NOTE: To calculate R-values of equivalent alternative
materials). The base must extend at least 18” beyond the front, rear and sides of the stove, and must extend
underneath and 2˝ beyond each side of horizontal connector pipe if it is elbowed towards a wall (see figure
5 and consult local building codes and fire protection ordinances.)
2. The stove must have its own flue.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING OTHER APPLIANCES.
3. After observing the clearances to combustible materials (figure 2 – 4), locate your floor protector accordingly
(figure 2) and carefully place the stove in your selected location. Install stove pipe, elbows, and thimble as
required, utilizing either a recently cleaned and inspected 6˝/152mm masonry chimney or a 6˝/152mm i.d.
manufacured chimney system listed to UL 103 HT. Maximum 64 square inches.
4. Use 6˝/152mm diameter minimum 24 MSG Black or 26 MSG Blue round stove pipe. DO NOT USE GALVANIZED
duct pipe. Secure pipe sections with three (3) sheet metal screws in each stove pipe and/or elbow joint to
firmly hold the pipe sections together. Screws may be no more than a maximum of 3˝/76mm apart.
DO NOT
CONNECT THIS STOVE TO ANY AIR DISTRIBUTION OR DUCT SYSTEM.
5. Recheck clearances from the stove, connector stove pipe, and corner clearances using the illustrations and
your local building codes or fire protection ordinances. NOTE: Drywall faced with brick or stone MUST be
considered a combustible surface.
6. DO NOT INSTALL THIS STOVE IN A MOBILE HOME, MANUFACTURED HOME, TENT OR TRAILER. (NO EXCEPTIONS)
7. The clearances provided are minimum dimensions. Installation of this stove must comply with your local
building code rulings.
8. This stove is NOT a UL listed stove.
MINIMUM CLEARANCES TO
COMBUSTIBLE SURFACES
Unit to Sidewall
36”
Unit to Backwall
36”
Unit Corner to Wall
36”
Pipe Connector to Backwall 38”
Pipe Connector to Ceiling
18”
Содержание THE RANCHER SR57E
Страница 19: ...19 NOTES ...