Ground the cable in accordance with grounding
instructions provided.
•
Torque terminals in accordance with the
information provided in
•
Follow the motor manufacturer wiring
requirements
represents line power input, motor, and
grounding for basic adjustable frequency drives. Actual
configurations vary with unit types and optional
equipment.
95
130BB920.10
+DC
BR-
B
M
A
I
N
S
L1 L2 L3
91 92 93
RELA
Y 1 RELA
Y 2
99
- LC -
U V
W
MO
TOR
99
Figure 2.8 Example of Motor, Line Power and Ground Wiring
2.4.4 AC Line Input Connection
•
Size wiring based upon the input current of the
adjustable frequency drive. For maximum wire
sizes, see
10.1 Power-dependent Specifications
.
•
Comply with local and national electrical codes
for cable sizes.
•
Connect 3-phase AC input power wiring to
terminals L1, L2, and L3 (see
•
Depending on the configuration of the
equipment, input power will be connected to the
line input power or the input disconnect.
•
Ground the cable in accordance with grounding
instructions provided in
•
All adjustable frequency drives may be used with
an isolated input source as well as with ground
reference power lines. When supplied from an
isolated line power source (IT line power or
floating delta) or TT/TN-S line power with a
grounded leg (grounded delta), set
14-50 RFI 1
to
[0] Off
. When off, the internal RFI filter capacitors
between the chassis and the intermediate circuit
are isolated to avoid damage to the intermediate
circuit and to reduce ground capacity currents in
accordance with IEC 61800-3.
2.4.5 Control Wiring
•
Isolate control wiring from high power
components in the adjustable frequency drive.
•
If the adjustable frequency drive is connected to
a thermistor, for PELV isolation, optional
thermistor control wiring must be reinforced/
double insulated. A 24 V DC supply voltage is
recommended.
2.4.5.1 Access
•
Remove access cover plate with a screw driver.
See
.
•
Or remove front cover by loosening attaching
screws. See
130B
T248.10
Figure 2.9 Control Wiring Access for A2, A3, B3, B4, C3 and C4
Enclosures
Installation
VLT
®
AutomationDrive Instruction
Manual
MG33AM22 - VLT
®
is a registered Danfoss trademark
2-7
2
2
Содержание FC 300
Страница 1: ...MAKING MODERN LIVING POSSIBLE Instruction Manual VLT AutomationDrive FC 300 0 25 75 kW ...
Страница 2: ......
Страница 8: ...Contents VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark ...
Страница 14: ...Introduction VLT AutomationDrive Instruction Manual 1 6 MG33AM22 VLT is a registered Danfoss trademark 1 1 ...
Страница 62: ...Status Messages VLT AutomationDrive Instruction Manual 7 4 MG33AM22 VLT is a registered Danfoss trademark 7 7 ...
Страница 109: ...Index VLT AutomationDrive Instruction Manual MG33AM22 VLT is a registered Danfoss trademark 12 5 ...
Страница 110: ...www danfoss com drives MG33AM22 130R0300 MG33AM22 Rev 2013 03 12 ...