Quick Installation Guide

TRIO-50.0/60.0-GROUNDING KIT

ABB solar inverters

1.

3.

2.

Main components

Assembly instructions

Assembly instructions

Supplied component list

EN 

Main components

01

Negative grounding board

02

Connection cable for negative pole

03

Signals wiring

04

Signals wiring connector

01

04

02

03

Components available in the kit

Quantity

Grounding board

1

Signals wiring

1

Components for mounting the cable to negative pole 

of DC disconnect switch:

Nut, threaded washer, cutted washer, metallic support 

1 + 1 + 1 + 1

In additio

n to what 

is explain

ed in this

 guide, th

e safety a

nd installa

tion inform

ation pro

vided in th

e installat

ion manu

al must be

 read and

 followed

.

The techn

ical docu

mentation

 and the in

terface an

d manage

ment softw

are for th

e product

 are availa

ble at the

 website.

XXXXXXX

XXXX

XXXX

XXXX

XXXXXX

XXXX

XXXXXX

XXX

ABB sola

r inverter

s

Quick Installation Guide

1

Access to the zones inside the inverter must be carried out with the equipment dis-

connected from the network and from the photovoltaic generator.

Isolate the inverter by externally disconnecting the side AC, DC and any voltages 

connected to the multifunction relay. Acting only on switches present on the inverter, 

some internal parts have hazardous voltages.

The GROUNDING KIT must be installed inside the DC wiring box.  

•  Before removing the front cover, place the DC 

disconnect switch to OFF position.  

In “ON” position, the switch does not allow the 

removal of the front cover.

•  Proceed to remove the 8 screws holding the 

front cover of the DC wiring box.

•  The grounding board must be installed on the 

appropriate holder positioned on the lower side 

of the communication and control card (area 

highlighted in the figure to the side).

•  Press down lightly on both sides of the 

board until the two holding clips will block 

the board to the support.

•  Connect the signals wiring between the 

grounding board and the communication and 

control board. One side of the signals wiring 

must be connected to the J13 connector on 

the grounding board; the other end must be 

connected to J1 connector present on the 

communication and control board.

•  Connect the cable present on the grounding 

board to negative pole placing the cable on 

the negative connection of the DC disconnec-

tor switch (first terminal at the top right of the 

disconnector switch). 

Observe the installation sequence shown in 

the figure. 

- Metallic support (tightening torque 4 Nm) 

 

- Toothed washer 

 

- Cable from the grounding board 

 

- Cutted washer 

 

- Hexagonal nut (tightening torque 4 Nm) 

 

The components required for the fixation of the cable are present in the materials supplied. 

•  Check the correct installation of the board, 

signals wiring and connection cable to the 

negative pole

In -SX version of the Wiring Box AC, a cartridge must be removed from the AC overvolt-

age dischargers (as described below)